4 simultaneous attempts to access the controller, Simultaneous attempts to access the controller – Festo Контроллеры двигателя SFC-LAC User Manual
Page 109
5. Commissioning
5−7
Festo GDCP−SFC−LACI−CO−EN en 0812NH
5.1.4
Simultaneous attempts to access the controller
Caution
Simultaneous or alternating attempts to access the
SFC−LACI via FCT, control panel and controller interface
can cause unpredictable errors.
·
Make sure that the FCT, the control panel and the conĆ
troller interface of the SFC−LACI are not used at the same
time.
Note
In the following cases, it is
not permitted to use the FCT to
access the SFC−LACI for purposes of writing data
(e.g.Ădownloading parameters) or for control (e.g.ĂMove
manually" or starting a homing run):
Ĉ While the SFC−LACI is executing a positioning motion or
when a motion is started during access (e.g.Ăvia the conĆ
trol interface or via the control panel).
Ĉ If parameterisation or operation is carried out on the
SFC−LACI with the control panel.
Please note:
·
Control by the FCT must not be activated while the drive
is in motion or when control is being carried out via the
fieldbus.