5. Commissioning

5−43

Festo GDCP−SFC−LACI−CO−EN en 0812NH

CPOS

Control byte 2 (CPOS) controls the positioning sequences as
soon as the drive is enabled.

Control byte 2 (CPOS)

Bit

EN

Description

B0
HALT

Halt

= 1: HOLD is not active
= 0: HALT is activated. The axis stops with a defined braking ramp, the

positioning job remains active (with B6 the remaining path can be
deleted).

B1
START

Start
Positioning
Task

With a

rising edge the current setpoint data will be transferred and posiĆ

tioning started (record 0 = homing).

B2
HOM

Start

Homing

With a

rising edge homing is started with the set parameters.

B3
JOGP

Jog positive

The drive moves at the specified speed in the direction of larger actual
values, providing the bit is set. The movement begins with the rising
edge and ends with the falling edge.

B4
JOGN

Jog negative

The drive moves in the direction of smaller actual values, see bitĂ3.

B5
TEACH

Teach Actual
Value

With a falling edge the current actual value of the position will be transĆ
ferred to the setpoint value register of the currently addressed positionĆ
ing record, see section 5.6.3.
The teach target is defined with PNU 520.

B6
CLEAR

Clear
Remaining
Path

In the HALT" status, a signal edge causes the positioning task to be
deleted and transfer to the Ready" status.

B7
ć

ć

Reserved, must be set to 0.