Bus status, Diagnostics and error display 6−6, Green bus ĉ operating status (status machine) – Festo Контроллеры двигателя SFC-LAC User Manual

Page 206: Red bus ĉ connection, Tab. 6/5: i/f" led

Advertising
background image

6. Diagnostics and error display

6−6

Festo GDCP−SFC−LACI−CO−EN en 0812NH

Bus status

I/F

1)

GREEN

Bus Ĉ operating status (status machine)

ON

OFF

ON

Operational"
Ĉ System in operational" status

ON

OFF

FLASHES
ONCE

Stopped"
Ĉ Master has sent Stop signal (transition status, system

again in pre−operational status).

ON

OFF

FLASHES

Pre−operational"
Ĉ SFC−LACI not yet set by CAN master to Operational

mode" (but SDOs are available).

I/F

1)

RED

Bus Ĉ connection

ON

OFF

OFF

Connection error−free

ON

OFF

FLASHES
ONCE

Warning Limit reached"
Ĉ Several communication errors have occurred or the

SFC−LACI receives no reply (master switched off or cable
break).

ON

OFF

FLASHES
TWICE

Node guarding error"
Ĉ Node Guarding error occurred (only if activated).

If occurring simultaneously, has priority over Warning
Limit reached"

ON

OFF

ON

Bus parameter not parameterised, bus failed or external
CAN supply missing
Ĉ e.g. at power−on, if not all bus parameters (node ID,

DS402/FHPP, baud rate) are parameterised.

1)

Two−colour LED as per DS 303−3. If occurring simultaneously, the red LED has priority ć no mixed"
display of red and green.

Tab. 6/5: I/F" LED