3. Installation

3−23

Festo GDCP−SFC−LACI−CO−EN en 0812NH

Fieldbus plug FBS−SUB−9−BU−2x5POL−B

(IP54)

·

Observe the fitting instructions for the fieldbus plug.
Tighten the two fastening screws at first by hand and
then with max. 0.4 Nm.

Note
The clamp strap in the fieldbus plug from Festo is conĆ
nected internally only capacitively with the metal housing
of the Sub−D plug. This is to prevent compensating curĆ
rents flowing through the screening of the fieldbus cable.

·

Clamp the screening of the fieldbus cable under the
clamp strap in the fieldbus plug. The SLD" terminal
in the fieldbus plug is optional.

1

Folding cover
with inspection
window

2

Clamp strap for
screen
connection

3

Blanking plug
if connection
unused

4

Fieldbus
continuing (OUT)

5

Fieldbus
incoming (IN)

6

Only capacitively
connected

V+

GND

H L

SLD

V+

GND

H L

SLD

2

1

3

4

5

6

Bus in

Bus out

Fig. 3/6:

Fieldbus plug type FBS−SUB−9−BU−2x5POL−B