5. Commissioning
5−45
Festo GDCP−SFC−LACI−CO−EN en 0812NH
5.5.6
Description of the status bytes SCON, SPOS, SDIR (RSB)
Status byte 1 (SCON)
Bit
EN
Description
B0
ENABLED
Drive
Enabled
= 0: Drive blocked, controller not active
= 1: Drive (controller) enabled
B1
OPEN
Operation
Enabled
= 0: STOP active
= 1: Operation enabled, positioning possible
B2
WARN
Warning
= 0: Warning not applied
= 1: Warning applied
B3
FAULT
Fault
= 0: No fault
= 1: A fault exists or a fault reaction is active. Fault number in
diagnostic memory
B4
24VL
Voltage Load
= 0: No load voltage
= 1: Load voltage applied
B5
HMI
Drive Control
= 0: Device control by PLC/fieldbus
= 1: Device control by FCT/MMI
B6
OPM1
Operating
Mode
= 00: Record select (standard)
= 01: Direct mode
10 Reserved
B7
OPM2
= 10: Reserved
= 11: Reserved