Festo Контроллеры двигателя SFC-LAC User Manual

Page 350

Advertising
background image

C. Object directory DS402 and CI

C−24

Festo GDCP−SFC−LACI−CO−EN en 0812NH

Receive PDO communication parameter

DS402

1400h,
1401h

01h...05h

Record

uint32, uint8, uint16

rw

Description

Communication parameters of PDOs 1 and 2 which the device can receive:
Ĉ PDO 1:

Object 1400h

Ĉ PDO 2:

Object 1401h

COB ID for PDO 1400h,

1401h

01h

uint32

COB ID used by the PDO.
Ĉ PDO 1:

Default: 0x200 + Node ID

Ĉ PDO 2:

Default: 0x300 + Node ID

Transmission type 1400h,

1401h

02h

uint8

Transmission type
Default: 255 (0xFF) ć Event−triggered asynchronous transmission
Value range: 0 ... 255 (0x00 ... 0xFF)

Inhibit time 1400h,

1401h

03h

uint16

Inhibit time, not used for RPDO. Fixed: 0 (0x0000).

(Reserved) 1400h,

1401h

04h

ć

Reserved

Event timer

1400h,
1401h

05h

uint16

Event counter in [ms]. Default: 0 (0x0000)