5. Commissioning

5−27

Festo GDCP−SFC−LACI−CO−EN en 0812NH

Device control

When the SFC−LACI is switched on, the controller interface is
activated as standard [HMI = off ].

Caution
Unexpected movements of the drive due to incorrect par−
ameterising

·

Make sure that there is no active ENABLE signal when
switching on the SFC−LACI on the controller interface.

·

Parameterise the entire system completely before actiĆ
vating the controller with ENABLE (controller interface),
Enable" (FCT), or [HMI = on] (control panel).

In order that the Festo Configuration Tool can control the conĆ
nected SFC−LACI, the control interface of the SFC−LACI must
be deactivated and control must be enabled for the FCT. The
actual status of the control bit ENABLE then has no effect.

·

To do this, go to the Project output" window, select the
Operate" tab and, under Device Control", activate the
FCT" checkbox.
The controller interface of the SFC−LACI will then be
deactivated and Control Enable will be set for the FCT.