5. Commissioning

5−53

Festo GDCP−SFC−LACI−CO−EN en 0812NH

Description to 3. Fault handling

Description of errors and warnings see section 6.3.

3.1

An error is shown with SCON.B3 FAULT.
} Positioning can no longer be undertaken.

3.2

A warning is shown with SCON.B2 WARN.
} Positioning can still be undertaken.

3.3

Acknowledge fault with positive edge at CCON.B3
(RESET).
} Fault bit SCON.B3 FAULT or SCON.B2 WARN is reset.
} SPOS.B2 MC will be set.
} Drive is ready to operate.

ć or ć

3.4

Acknowledge fault with negative edge at CCON.B0
ENABLE.
} Fault bit SCON.B3 FAULT or SCON.B2 WARN is reset.
} SPOS.B2 MC will be set.
} Create readiness again
(see examples 1, Tab. 5/4 and 2, Tab. 5/5)

Caution
After the removal of ENABLE, the drive is no longer under
position control. This may cause injury to people and maĆ
terial damage.

Ĉ With vertical or sloping drive mountings, the moving

mass could possibly slide down.