B. Parametrising as per FHPP−FPC
B−82
Festo GDCP−SFC−LACI−CO−EN en 0812NH
Drive data (data of the SFC−LACI)
PNU
1026
Various
uint32
r(w)
Description
General data of the SFC−LACI.
Output stage
temp
1026
1 (CI:01h)
r
temp.
Temperature of the SFC−LACI in °C. Range: −20...+120 °C
Output stage
max temp
1026
2 (CI:02h)
r
max. temp.
Highest temperature measured to date for the SFC−LACI, in °C. Stored in
EEPROM.
Max. current
1026
4 (CI: 04h)
rw
Current limiting. Identical to PNU 1034 / 6073h and 6510/41h.
Device control 1026
6 (CI: 06h)
rw
Identical to PNU 125 / 207Dh.
Bit 0 = 0: Control interface OFF, control via HMI or FCT ON
Bit 0 = 1: Control interface ON
To enable FCT control after the control interface has been switched off, set
ENABLE OPERATION in the Control Word as well (object 6040h).
Controller serial
number
1026
7 (CI: 07h)
r
number
Serial number of the SFC−LACI
CI / DS402
6510h
Various
uint32
r(w)
Further subindices of 6510h: see section C.3.
I2t value
PNU
1027
ć
uint32
r
Description
Actual I
2
t value. See PNU 1025/4.
CI / DS402
6410h
04h
uint32
r