Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4A0930

R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31

4/0 × 4P×2

3/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 4P×2

3/0 to 300

⊖, ⊕1

4/0 to 300

⊕3

4/0 to 300

3/0

3/0 to 250

4A1200

R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31

300 × 4P×2

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 4P×2

4/0 to 300

⊖, ⊕1

250 to 300

⊕3

4/0 to 300

4/0

4/0 to 250

<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI or use 10 mm

2

(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.

Note:

When connecting peripheral devices or options to terminals

⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For

more information, contact Yaskawa or your nearest sales representative.

n

Three-Phase 600 V Class

Table 3.5 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

5A0003
5A0004
5A0006

R/L1, S/L2, T/L3

14

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

5A0009

R/L1, S/L2, T/L3

14

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

12 to 10

5A0011

R/L1, S/L2, T/L3

10

14 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

14

14 to 6

⊖, ⊕1, ⊕2

14 to 6

B1, B2

14 to 10

8

12 to 8

M5

2.0 to 2.5

(17.7 to 22.1)

5A0017

R/L1, S/L2, T/L3

10

10 to 6

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

10

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

10 to 8

2.7 to 3.0

(23.9 to 26.6)

8

12 to 8

M6

5.4 to 6.0

(47.8 to 53.1)

5A0022

R/L1, S/L2, T/L3

8

10 to 6

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

10

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

10 to 8

2.7 to 3.0

(23.9 to 26.6)

8

10 to 6

M6

5.4 to 6.0

(47.8 to 53.1)