Auto-tuning, Types of auto-tuning, 8 auto-tuning – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 285: Auto-tuning for induction motors

Advertising
background image

5.8 Auto-Tuning

u

Types of Auto-Tuning

The drive offers different types of Auto-Tuning for induction motors. Refer to the tables below to select the type of Auto-

Tuning that bests suits the application.

n

Auto-Tuning for Induction Motors

This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.

Table 5.8 Types of Auto-Tuning for Induction Motors

Type

Setting

Application Conditions and Benefits

Control Mode

V/f

OLV

Stationary Auto-Tuning for

Line-to-Line Resistance

T1-01 = 2

• The drive is used in V/f Control and other Auto-Tuning selections are

not possible.

• Perform when entering motor data manually while using motor cables

longer than 50 m.

• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been

replaced with a cable over 50 m long. Assumes Auto-Tuning has

already been performed.

• Should not be used for any vector control modes unless the motor cable

has changed.

YES

YES

Rotational Auto-Tuning for

V/f Control

T1-01 = 3

• Recommended for applications using Speed Estimation Speed Search

or using the Energy Saving function in V/f Control.

• Assumes motor can rotate while Auto-Tuning is executed. Increases

accuracy for certain functions like torque compensation, slip

compensation, Energy Saving, and Speed Search.

YES

Stationary

Auto-Tuning 2

T1-01 = 4

• Motor and load cannot be decoupled and the load is higher than 30%.
• A motor test report is available. After entering the no-load current and

the rated slip, the drive calculates and sets all other motor-related

parameters.

YES

Table 5.9

lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.

The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor

manufacturer.

Table 5.9 Auto-Tuning Input Data

Input Value

Input Parameter

Unit

Tuning Type (T1-01)

2

Line-to-Line

Resistance

3

Rotational for V/f

Control

4

Stationary 2

Control Mode

A1-02

0, 2

0

2

Motor rated power

T1-02

kW

YES

YES

YES

Motor rated voltage

T1-03

Vac

YES

YES

Motor rated current

T1-04

A

YES

YES

YES

Motor rated frequency

T1-05

Hz

YES

YES

Number of motor poles

T1-06

-

YES

YES

Motor rated speed

T1-07

r/min

YES

YES

Motor no-load current

T1-09

A

YES

Motor rated slip

T1-10

Hz

YES

Motor iron loss

T1-11

W

YES

5.8 Auto-Tuning

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

285

5

Troubleshooting