No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-06

(07D6)

Soft Charge Bypass

Relay Maintenance

ChgCirc Life Mon

Displays the soft charge bypass relay maintenance time as a

percentage of its estimated performance life. Parameter o4-07

can be used to reset this monitor.

Replace the soft charge bypass relay when this monitor reaches

90%.

No signal output

available

1%

U4-07

(07D7) IGBT Maintenance

IGBT Life Mon

Displays IGBT usage time as a percentage of the expected

performance life. Parameter o4-09 can be used to reset this

monitor.

Replace the IGBT when this monitor reaches 90%.

No signal output

available

1%

U4-08

(0068)

Heatsink Temperature

Heatsink Temp

Displays the heatsink temperature.

10 V: 100 °C

1 °C

U4-09

(005E) LED Check

LED Oper Check

Lights all segments of the LED to verify that the display is

working properly. Press the ENTER key to turn the LEDs on

and press ESC to turn the LEDs off.

No signal output

available

U4-10

(005C) kWh, Lower 4 Digits

kWh Lower 4 dig

Monitors the drive output power usage (or consumption). The

value is shown as a 9-digit number displayed across two monitor

parameters, U4-10 and U4-11.

Example:

12345678.9 kWh is displayed as:

U4-10: 678.9 kWh

U4-11: 12345 MWh

No signal output

available

1 kWh

U4-11

(005D) kWh, Upper 5 Digits

kWh Upper 5 dig

No signal output

available

1 MWh

U4-13

(07CF) Peak Hold Current

Current PeakHold

Displays the highest current value that occurred during run.

Note:

The unit is expressed in 1 A for models 4A0930

and 4A1200.

No signal output

available

0.01 A

<3> <4>

<5>

U4-14

(07D0)

Peak Hold Output

Frequency

Freq@ I PeakHold

Displays the output frequency when the current value shown in

U4-13 occurred.

No signal output

available

0.01 Hz

U4-16

(07D8)

Motor Overload

Estimate (oL1)

Motor OL1 Level

Shows the value of the motor overload detection accumulator.

100% is equal to the oL1 detection level.

10 V: 100%

0.1%

U4-18

(07DA)

Frequency Reference

Source Selection

Reference Source

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

1 = Reference 1 (b1-01)

2 = Reference 2 (b1-15)

Y-nn: indicates the reference source

0-01 = Digital operator

1-00 = Analog (Not displayed in models 4A0930 and 4A1200)

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

1-03 = Analog (terminal A3)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

5-01 = Pulse input

9-01 = Up/Down Command (Not displayed in models 4A0930

and 4A1200)

No signal output

available

U4-19

(07DB)

Frequency Reference

from MEMOBUS/

Modbus Comm.

MEMOBUS Freq Ref

Displays the frequency reference provided by MEMOBUS/

Modbus (decimal).

No signal output

available

0.01%

U4-20

(07DC)

Option Frequency

Reference

Option Freq Ref

Displays the frequency reference input by an option card

(decimal).

No signal output

available

B.15 U: Monitors

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide