Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 177

Advertising
background image

13.

The pump can be run in HAND (LOCAL) Mode for maintenance purposes by pressing the HAND key while the drive

is stopped. The HAND key acts as a start button. Press the OFF button to stop the drive. Press AUTO to return the

drive to geothermal control. The HAND speed reference can be set in P5-02 (Hand Reference 1). Disable the HAND

key by setting P5-04 to 0 (disabled).

Related Parameters, Faults, and Alarms

No.

Parameter Name

Setting Values

A1-01

Access Level Selection

Default: 2

Range: 0 to 3

A1-03

Initialize Parameters

Default: 0

Range: 0 to 5550; 6008 to 6011; 7770

b1-02

Run Command Selection 1

Default: 0

Range: 0 to 3

E2-01

Motor Rated Current

Default:

Min.: 10% of drive rated current

Max.: 200% of drive rated current

E2-04

Number of Motor Poles

Default: 2

Min.: 2

Max.: 48

P1-03

Feedback Device Scaling

Default: 145.0 PSI

Min.: 0.1

Max.: 6000.0

P1-04

Start / Draw Down Level

Default: 0.0

Min.: -999.9

Max.: 999.9

P1-06

Minimum Pump Speed

Default: 40.0 Hz

Min.: 0.0

Max.: [E1-04]

P1-11

High Feedback Level

Default: 0.0 PSI

Min.: 0.0

Max.: 6000.0

P2-02

Sleep Level

Default: 0.0 Hz

Min.: 0.0

Max.: 6000.0

P4-10

AUTO Mode Operator Run Power Down Storage

Default: 0

Range: 0, 1

P5-02

HAND Speed Reference 1

Default: 40.0 Hz

Min.: 0

Max.: [E1-04]

P5-04

HAND Key Function Selection

Default: 1

Range: 0, 1

Q1-01

PID Controller Setpoint 1

Default: 0.0

Min.: 0.0

Max.: 6000.0

Q2-01

Minimum Geothermal Temperature Input

Default: 0.0 °F

Min.: -110.0

Max.: 275.0

Q2-02

Maximum Geothermal Temperature Input

Default: 120.0 °F

Min.: -100.0

Max.: 275.0

Q2-03

Minimum Geothermal Speed

Default: 40.0 Hz

Min.: 0.0

Max.: 400.0

Q2-04

Maximum Geothermal Speed

Default: 60.0 Hz

Min.: 0.0

Max.: 400.0

Q2-05

Low Temperature to Run at Maximum Geothermal Speed

Default: 55.0 °F

Min.: -110.0

Max.: 275.0

4.5 iQpump Presets and Functions

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

177

4

Start-Up Programming & Operation

Advertising