P4-10: AUTO Mode Operator Run Power Down Storage

Selects drive response to power loss with regards to the Run command. When running in AUTO Mode and using a Run

command from the keypad (b1-02 = 0), P4-10 determines whether the drive will automatically start running when power is

reapplied. The factory setting of this parameter requires pressing the AUTO key to start the drive after power loss.

WARNING! Sudden Movement Hazard. If the drive is running at power loss, it will automatically initiate an internal Run command upon

power-up if P4-10 = 1 (Enabled) and could result in death or serious injury from moving equipment.

No.

Parameter Name

Setting Range

Default

P4-10

AUTO Mode Operator Run Power Down Storage

0, 1

0

Setting 0: Disabled
Setting 1: Enabled

n

P4-12: Thrust Bearing Frequency

Sets the frequency used by the drive when determining which acceleration and deceleration time to use. The Thrust Bearing

function is used for applications using submersible motors. The function provides an alternate acceleration time (P4-11) and

deceleration time (P4-13) for protecting the pump bearings.
At start, the drive will use the P4-11 acceleration time until the P4-12 frequency is reached, at which time it will use the active

C1-oo acceleration and deceleration times. At stop, if the output frequency is above the P4-12 setting, the active C1-oo

deceleration time will be used until the P4-12 setting is reached at which time it will use the P4-13 time setting for the rest of

deceleration.
If P4-12 is set greater than P1-06 (minimum Pump Speed), P4-12 will become the frequency lower limit. The drive PID control

must be disabled (b5-01 = 0) for this function to work.

No.

Parameter Name

Setting Range

Default

P4-12

Thrust Bearing Frequency

0.0 to E1-04

30.0 Hz

R un

C omm an d

T hrust B ea ring

R am p T o Stop (b1-03 = 0)

“T hrust Active”

M essage &

D igital Ou tpu t

(H 2-0x = A9)

Ou tpu t

F requen cy

P4-11

P4-13

P4-12 – T hrust F requen cy

C 1-01

(or selected)

Accel R ate

C 1-02

(or selected)

D ecel R ate

Figure 4.51 Thrust Bearing

n

P4-17: Utility Start Delay

Sets the delay time after power up until the drive will recognize a Run command present within one second of power up or

when the Run command is jumpered on the terminal strip.
This is useful in preventing a peak power surge when multiple drives power up and begin accelerating simultaneously. This

function works when the drives all have different P4-17 settings to spread out the power draw during acceleration.
If the Run command is removed and re-applied during the P4-17 time, the drive will cancel the utility start delay and

immediately begin running.
The Utility Start Delay is applied when the drive is auto-restarting after an Undervoltage (Uv) or an Overvoltage (ov) condition.

No.

Parameter Name

Setting Range

Default

P4-17

Utility Start Delay

0.0 to 1000.0 min

0.2 min

n

P5-02: HAND Reference 1

Sets the frequency reference of HAND mode. When the drive is stopped, pressing the HAND key will start the drive and the

drive will accelerate to the P5-02 setting.

4.6 Basic iQpump Setup and Application Preset Parameters