Related Parameters, Faults, and Alarms

No.

Parameter Name

Setting Values

P4-21

Low City Input Select

Default: 1

Range: 0, 1

P4-22

Low City On-Delay Time

Default: 10 s

Min.: 1

Max.: 1000

P4-23

Low City Off-Delay Time

Default: 5 s

Min.: 0

Max.: 1000

P4-24

Low City Alarm Text

Default: 0

Range: 0 to 2

H1 Multi-Function Digital Input Settings

H1-oo

Setting

Function

Description

73

Low City Press

Indicates that sufficient or insufficient pressure is present on the inlet to the pump. Used mainly for pressure

booster situations.

HOA Keypad Display

Minor Fault Name

Low City Pressure

Low City Pressure

Cause

Possible Solution

Insufficient pressure is present on the inlet

to the pump.

• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.

HOA Keypad Display

Minor Fault Name

Low Suction Pressure

Low Suction Pressure

Cause

Possible Solution

Insufficient suction pressure is present.

• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.

HOA Keypad Display

Minor Fault Name

Low Water in Tank

Low Water in Tank

Cause

Possible Solution

The water level in the tank is too low.

• Check pressure switch contact for correct operation.
• Check control wiring to drive terminal strip from pressure switch contact.
• Check to make sure that suction pressure is present by means of a separate measuring device.

n

Current Limit

This function provides a current limit of the pump (motor). The function is designed to prevent long-term overload conditions

of the pump, especially if the motor and drive are oversized compared to the pump. The drive will attempt to limit the output

current by reducing the frequency reference. The frequency is reduced using an internal current PI regulator. When the Current

Limit function is active, the alarm "Current Limit Foldback" will be displayed on the HOA keypad. This function will only

operate correctly when the drive is connected to a variable torque motor load such as a centrifugal pump. More specifically,

it will only operate if the load is such that output current increases as output frequency increases (and vice-versa). The current

limit function reduces the pump speed to just above the lower value between the minimum pump speed (P1-06) or the minimum

output frequency. If PI mode is enabled (b5-01 > 0), a special limit will be applied to the PID integrator when output current

limit is active to prevent integrator wind-up.

Start Up Procedure

1.

Set all other parameters required for the application such as PI control loop, sleep, motor, and I/O parameters

2.

Turn on the current limit function by setting Q3-01 to 1 (enabled). The default setting is 0 (disabled).

3.

Set the desired current limit in Q3-02. This value should not exceed the motor, pump or drive’s ratings. This does not

in any way change the motor (oL1) and inverter (oL2) overload functions.

4.

If desired, program a multi-function digital output (H2-oo) to 89 (Output Current Limit) to annunciate the alarm.

4.5 iQpump Presets and Functions

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

185

4

Start-Up Programming & Operation