L4: speed detection – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 363

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L3-11

(04C7)

Overvoltage

Suppression Function

Selection

OV Inhibit Sel

0: Disabled

1: Enabled

Enables or disables the ov suppression function, which allows

the drive to change the output frequency as the load changes to

prevent an ov fault.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

L3-17

(0462)

Target DC Bus Voltage

for Overvoltage

Suppression and Stall

Prevention

DC Bus Reg Level

Sets the desired value for the DC bus voltage during overvoltage

suppression and Stall Prevention during deceleration.

Default: 375 Vdc

<2> <3>

Min.: 150
Max.: 400

<3>

L3-20

(0465)

DC Bus Voltage

Adjustment Gain

DC Bus P Gain

Sets the proportional gain for KEB Ride-Thru, Stall Prevention,

and overvoltage suppression.

Default: 1.00

(V/f)

0.30 (OLV)

Min.: 0.00

Max.: 5.00

L3-21

(0466)

Accel/Decel Rate

Calculation Gain

Acc/Dec P Gain

Sets the proportional gain used to calculate the deceleration rate

during KEB Ride-Thru, ov suppression function, and Stall

Prevention during deceleration (L3-04 = 2).

Default: 1.00

Min.: 0.10

Max.: 10.00

L3-23

(04FD)

Automatic Reduction

Selection for Stall

Prevention during Run

CHP Stall P Sel

0: Lv1 set in L3-06

1: Autom. Reduction

V/f

V/f

0: Sets the Stall Prevention level set in L3-06 that is used

throughout the entire frequency range.

1: Automatic Stall Prevention level reduction in the constant

output range. The lower limit value is 40% of L3-06.

Default: 0

Range: 0, 1

L3-24

(046E)

Motor Acceleration

Time for Inertia

Calculations

Mtr Accel Time

Sets the time needed to accelerate the uncoupled motor at rated

torque from stop to the maximum frequency.

Default:

<4> <5>

Min: 0.001 s

Max: 10.000 s

L3-25

(046F) Load Inertia Ratio

Load Inertia Rat

Sets the ratio between the motor and machine inertia.

Default: 1.0

Min.: 1.0

Max.: 1000.0

L3-26

(0455)

Additional DC Bus

Capacitors

ExtDC busCapSize

When DC bus capacitors have been added externally, be sure to

add those values to the internal capacitor table for proper DC

bus calculations.

Default: 0 μF

Min: 0

Max: 65000

L3-27

(0456)

Stall Prevention

Detection Time

Stl Prev DetTime

Sets the time the current must exceed the Stall Prevention level

to activate Stall Prevention.

Default: 50 ms

Min.: 0

Max.: 5000

<1> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but

set the value below 1040 Vdc (overvoltage protection level).

<4> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<5> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-01

(0499)

Speed Agreement

Detection Level

Spd Agree Level

L4-01 sets the frequency detection level for digital output

functions H2-oo = 2, 3, 4, 5.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

L4-02

(049A)

Speed Agreement

Detection Width

Spd Agree Width

L4-02 sets the hysteresis or allowable margin for speed

detection.

Default: 2.0

Min.: 0.0

Max.: 20.0

L4-03

(049B)

Speed Agreement

Detection Level (+/-)

Spd Agree Lvl+-

L4-03 sets the frequency detection level for digital output

functions H2-oo = 13, 14, 15, 16.

Default: 0.0 Hz

Min.: -400.0

Max.: 400.0

L4-04

(049C)

Speed Agreement

Detection Width (+/-)

Spd Agree Wdth+-

L4-04 sets the hysteresis or allowable margin for speed

detection.

Default: 2.0

Min.: 0.0

Max.: 20.0

B.8 L: Protection Function

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

363

B

Parameter List