B.14 T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance.

u

T1: Induction Motor Auto-Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

T1-01

(0701)

Auto-Tuning Mode

Selection

Tuning Mode Sel

0: Standard Tuning

1: Tune-No Rotate1

2: Term Resistance

3: V/f Engy Sav Tun

4: Tune-No Rotate2

0: Standard

1: Tune-No Rotate1

2: Stationary Auto-Tuning for Line-to-Line Resistance

3: Rotational Auto-Tuning for V/f Control Energy Saving

4: Tune-No Rotate2

Default:

<1>

Range: 0 to 4

T1-02

(0702)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power as specified on the motor nameplate.

Note:

Use the following formula to convert horsepower

into kilowatts:

1HP = 0.746 kW.

Default:

<2>

Min.: 0.00 kW

Max.: 650.00

kW

T1-03

(0703)

Motor Rated Voltage

Rated Voltage

Sets the motor rated voltage as specified on the motor

nameplate.

Default: 200.0
V

<3>

Min: 0.0
Max: 255.0

<3>

T1-04

(0704)

Motor Rated Current

Rated Current

Sets the motor rated current as specified on the motor

nameplate.

Default:

<2>

Min.: 10% of

drive rated

current

Max.: 200% of

drive rated

current

T1-05

(0705)

Motor Base Frequency Rated Frequency

Sets the rated frequency of the motor as specified on the motor

nameplate.

Default: 60.0 Hz

Min.: 0.0

Max.: 400.0

T1-06

(0706)

Number of Motor

Poles

Number of Poles

Sets the number of motor poles as specified on the motor

nameplate.

Default: 4

Min.: 2

Max.: 48

T1-07

(0707)

Motor Base Speed

Rated Speed

Sets the rated speed of the motor as specified on the motor

nameplate.

Default: 1750 r/

min

Min.: 0

Max.: 24000

T1-09

(0709)

Motor No-Load Current

(Stationary Auto-

Tuning)

Motor No-Load

Current

OLV

OLV

OLV

OLV

Sets the no-load current for the motor. After setting the motor

capacity to T1-02 and the motor rated current to T1-04, this

parameter will automatically display the no-load current for a

standard 4-pole Yaskawa motor. Enter the no-load current as

indicated on the motor test report.

Default: –

Min.: 0 A

Max.: T1-04

T1-10

(070A)

Motor Rated Slip

(Stationary Auto-

Tuning)

Motor Rated Slip

OLV

OLV

OLV

OLV

Sets the motor rated slip. After setting the motor capacity to

T1-02, this parameter will automatically display the motor slip

for a standard 4-pole Yaskawa motor. Enter the motor slip as

indicated on the motor test report.

Default: –

Min.: 0.00 Hz

Max.: 20.00 Hz

T1-11

(070B) Motor Iron Loss

Mtr Iron Loss(W)

V/f

V/f

Sets the iron loss for determining the Energy Saving coefficient.

The value is set to E2-10 (motor iron loss) set when the power

is cycled. If T1-02 is changed, a default value appropriate for

the motor capacity that was entered will appear.

Default: 14 W

<4>

Min.: 0

Max.: 65535

<1> Default depends on parameter A1-02, Control Mode Selection.

Setting 0 (V/f): Default is 2.
Setting 2 (OLV): Default is 0

<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> Default setting value differs depending on the motor code value and motor parameter settings.