HOA Keypad Display

Fault Name

Uv2

Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.

Cause

Possible Solution

In drive models 2A0004 to 2A0056 or

4A0002 to 4A0031, L2-02 was changed

from its default value without installing a

Momentary Power Loss Ride-Thru unit

Correct the setting to L2-02 or install an optional Momentary Power Loss Ride-Thru unit.

Control power supply wiring is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the control board, the entire drive, or the control power supply. For

instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.

Internal circuitry is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

Uv4

<1>

Gate Drive Board Undervoltage
Voltage drop in the gate drive board circuit

Cause

Possible Solution

Not enough power is being supplied to the

gate drive board.

• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the gate drive board or the entire drive. For instructions on replacing

the gate drive board, contact Yaskawa or a Yaskawa representative.

<1> Detected in models 4A0930 and 4A1200.

HOA Keypad Display

Fault Name

Uv3

Undervoltage 3 (Soft-Charge Bypass Circuit Fault)
The soft-charge bypass circuit failed.

Cause

Possible Solution

The relay or contactor on the soft-charge

bypass circuit is damaged

• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

VLTS

Volute-Thermostat Fault

Cause

Possible Solution

The digital input assigned to the volute/

thermostat input (H1-0o = 88 or 89) is

active.

Check the wiring or wait for the volute or motor to cool.

Both volute/thermostat inputs are

programmed simultaneously (H1-0o = 88

and 89).

• Program only one digital input to either H1-0o = 88 or H1-0o = 89.
• Auto-restart of this fault is controlled by parameter L5-53, Volute-TStat Retry Selection.

HOA Keypad Display

Fault Name

voF

Output Voltage Detection Fault
Problem detected with the voltage on the output side of the drive.

Cause

Possible Solution

Hardware is damaged. Internal drive

module MC / FAN overheat protection

circuit board is due to abnormal ambient

operating power.

• Lower ambient temperature.
• Replace the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or a Yaskawa representative.

5.2 Fault Detection

258

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide