No.

Parameter Name

Setting Values

Q4-06

Wake-Up Water Level

Default: 30.0 ft

Min.: 0.0

Max.: 1200.0

Q4-07

Water Level Control Sleep Wake-Up Time

Default: 1 s

Min.: 0

Max.: 3600

Q4-08

Level Control Minimum Speed

Default: 0.00 Hz

Min.: 0.00

Max.: 400.00

Q4-09

Low Level Detection Level

Default: 0.0 ft

Min.: 0.0

Max.: 1200.0

Q4-10

Low Level Detection Time Delay

Default: 0.0

Min.: 0.0

Max.: 300.0

Q4-11

Low Level Behavior

Default: 1

Range: 0 to 3

Q4-12

Water Level Control Auto-Restart Time

Default: 5.0 min

Min.: 0.1

Max.: 6000.0

Q4-15

Low Water Level Detection Time Unit

Default: 0

Range: 0, 1

U1-01

Frequency Reference

10 V: Max frequency

U1-97

Water Level

Full scale:

10 V = Q4-02

u

iQpump Functions

n

Low City or Low Suction Inlet Pressure

This function is used with low suction inlet pressure switches on pressure booster systems for buildings that get their main

water supply from a municipality. This pressure switch enables and disables the pump system when the inlet supply is at a

low demand and when running the pump system in this condition will cause damage.
An inlet pressure switch is wired directly into the drive using one of the digital input terminals. If the pressure switch is active

and sufficient pressure is available, the drive system will operate normally. If the pressure switch indicates that incoming

pressure is too low, the drive will take the following actions:
• The drive will be forced into a sleep-like state (coast to stop).
• Any drives staged in multiplex mode will immediately coast to stop.
• The selected alarm “Low City Pressure”, “Low Suction Pressure”, or “Low Water In Tank” will be displayed (determined

by P4-24).

All drives will restart when sufficient pressure returns.

Required Control Wiring

Any one of the multi-function digital inputs (S1 to S8) must be wired and programmed with a low suction inlet pressure switch.

The appropriate terminal parameter (H1-oo) must be to set 73 (Low City Pressure). The action of the switch (normally open /

normally closed) is set in parameter P4-21.

Start Up Procedure

1.

Set all other parameters required for the application such as PI control loop, sleep, motor, and I/O parameters.

2.

Set one digital input for the low suction inlet pressure switch (H1-oo = 73). Wire the switch to this terminal.

3.

Configure the terminal for a normally open / closed switch type using parameter P4-21.

4.

Configure the delay times for activating and removing the alarm in parameters P4-23 and P4-24. This can be used to

stop the drive from cycling too frequently if the pressure varies a lot.

5.

Select the alarm message that will be displayed when a Low City condition is detected using parameter P4-24. Options

include “Low Cty Pressure”, “Low Suction Pres”, and “Low Watr In Tank”.

4.5 iQpump Presets and Functions

184