U1 - 92 – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 403

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U1-80

(0B9B)

Geothermal

Temperature Input

Geothermal Temp

Displays the geothermal temperature input after the gain and

bias have been applied. This temperature is used by the

Geothermal Function to determine the proper frequency at

which to run the drive.

This monitor is internally limited to -999.9 °F to +999.9 °F.

No signal output

available

0.1 °F

U1-83

(0B9E) Flow Rate

Flow Rate

Displays the flow rate based on the pulse input frequency or the

analog voltage (flow rate input) and parameters P6-01 and

P6-04.

A 2-second first order filter will be applied to this monitor.

Full scale: P6-01 dep. on

P6-04

U1-84

(0B9F)

Accumulation Level -

Millions

Volume * 1000000

Displays the recorded volume from the flow meter (pulse input

or analog voltage).

Total volume is calculated as follows:

Total Volume = (U1-84 * 1000000) + (U1-85 * 1000) + U1-86

+ U1-87

No signal output

available

dep. on

P6-16

U1-85

(0BA0)

Accumulation Level -

Thousands

Volume * 1000

U1-86

(0BA1)

Accumulation Level -

Ones

Volume * 1

U1-87

(0BA2)

Accumulation Level -

Decimal

Volume * 0.0001

U1-90

(0BA5) Pump Setpoint

Pump Setpoint

Displays the PID Setpoint.

No signal output

available

dep. on

P1-02

U1-91

(0BA6) Pump Feedback

Pump Feedback

Displays the PID Feedback.

No signal output

available

dep. on

P1-02

U1-92

(0BA7) Pump Status

Pump Status

Displays Pump Running Status.

U1 - 92=

00000000

Drive

Pump 2

Pump 3

Pump 4

Pump 5

Pump 6

Not used

Not used

1
1
1
1
1
1
0
0

No signal output

available

U1-93

(0BA8)

Total Setpoint

Compensation

Total SP Comp.

Displays the total absolute Setpoint Compensation.

No signal output

available

dep. on

P1-02

U1-94

(0BA9) Motor Speed

Motor Speed

Displays the absolute value of the output frequency (U1-02)

converted to RPM.

No signal output

available

1 RPM

U1-97

(0BAC) Water Level

Water Level

Displays the amount of water above the water level sensor.

Full scale:

10 V = Q4-02

0.1 ft.

U1-98

(0BAD) Suction Pressure

Suction Pressure

Displays the amount of suction pressure.

Full scale:

10 V = Q5-02

0.1 PSI

or ”Hg

U1-99

(0BAE) Anti-No-Flow Timer

ANF Timer

The Anti-No-Flow reduces the output frequency when this

value reaches the P2-24 setting.

No signal output

available

0.1 s

<1> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable

motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.

<5> Available in drive software versions PRG: 8551 and later.

B.15 U: Monitors

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

403