(2) GROUND
TERMINALS
CONTROL CIRCUIT
TERMINALS
MAIN CIRCUIT
TERMINALS
SECTION B-B
Unit: in. [mm]
Figure 2.36 Model 4T0058
Table 2.19 12-Pulse Model 4T0058 Terminal and Wire Specifications for Main Circuit and Ground
Drive Model
Terminal
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4T0058
<1>
R/L1, S/L2, T/L3
10 to 1/0 (5.3 to 53.5)
M8
9 to 11
(79.7 to 97.4)
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
B1, B2
22 to 10 (0.3 to 5.3)
M4
1.2 (10.6)
Refer to applicable codes for wire size
M8
9 to 11
(79.7 to 97.4)
<1> Refer to manual TOEP C710616 50 for information on 12-pulse models.