Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 396

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S2-05

(320A)

Sequence Timer 1

Reference Source

Tmr 1 Ref Source

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial com

6: Option PCB

7: Pulse Input

8: Set by b1-01

Selects the frequency reference source used for running the

drive when sequence timer 1 is active (only applicable when

S2-04 is set to 1 or 2).

0: Operator (d1-01/Q1-01)

1: Operator (d1-02/Q1-02)

2: Operator (d1-03/Q1-03)

3: Operator (d1-04/Q1-04)

4: Terminals

5: Serial communication

6: Option card

7: Pulse input

8: Set by b1-01

Default: 8

Range: 0 to 8

S2-06

(320B)

Sequence Timer 2 Start

Time

Tmr 2 Start Time

Sets the start time for timer 2. The value must be set less than

or equal to S2-07.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-07

(320C)

Sequence Timer 2 Stop

Time

Tmr 2 Stop Time

Sets the stop time for timer 2. The value must be set greater than

or equal to S2-06.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-08

(320D)

Sequence Timer 2 Day

Selection

Tmr 2 Day Sel

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Sets the days for which sequence timer 2 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

S2-09

(320E)

Sequence Timer 2

Selection

Tmr 2 Seq Sel

0: Digital out only

1: Run

2: Run - PI Disable

Sets the action that occurs when sequence timer 2 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

S2-10

(320F)

Sequence Timer 2

Reference Source

Tmr 2 Ref Source

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial com

6: Option PCB

7: Pulse Input

8: Set by b1-01

Selects the frequency reference source used for running the

drive when sequence timer 2 is active (only applicable when

S2-09 is set to 1 or 2).

0: Operator (d1-01/Q1-01)

1: Operator (d1-02/Q1-02)

2: Operator (d1-03/Q1-03)

3: Operator (d1-04/Q1-04)

4: Terminals

5: Serial communication

6: Option card

7: Pulse input

8: Set by b1-01

Default: 8

Range: 0 to 8

S2-11

(3210)

Sequence Timer 3 Start

Time

Tmr 3 Start Time

Sets the start time for timer 3. The value must be set less than

or equal to S2-12.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-12

(3211)

Sequence Timer 3 Stop

Time

Tmr 3 Stop Time

Sets the stop time for timer 3. The value must be set greater than

or equal to S2-11.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-13

(3212)

Sequence Timer 3 Day

Selection

Tmr 3 Day Sel

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Sets the days for which sequence timer 3 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

S2-14

(3213)

Sequence Timer 3

Selection

Tmr 3 Seq Sel

0: Digital out only

1: Run

2: Run - PI Disable

Sets the action that occurs when sequence timer 3 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

B.13 S: Special Application

396

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide