The following simultaneous contradictory

settings:
• H3-02, H3-10, or H3-06 = B (PID Feedback)

while H6-01

(Pulse Train Input) = 1 (PID Feedback)

• H3-02, H3-10, or H3-06 = C (PID Target Value)

while H6-01 = 2

(pulse train input sets the PID target value)

• H3-02, H3-10, or H3-06 = C (PID Target Value)

while b5-18 = 1

(enables b5-19 as the target PID value)

• H6-01 = 2 (PID target) while b5-18 = 1

(enables b5-19 as the target PID value)

Disable one of the PID selections.

HOA Keypad Display

Error Name

oPE09

PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4).

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function

Operation Level)

• The stopping method is set to either DC

Injection Braking or coast to stop with a timer

(b1-03 = 2 or 3).

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).

b5-01 is set to 1 or 2, enabling PID control, but the

lower limit for the frequency reference (d2-02) is

not set to 0 while reverse output is enabled (b5-11

= 1).

Correct the parameter settings.

b5-01 is set to 3 or 4, enabling PID control, but the

lower limit for the frequency reference (d2-01) is

not 0.

Correct the parameter settings.

HOA Keypad Display

Error Name

oPE10

V/f Data Setting Error
One of the following setting errors has occurred:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Cause

Possible Solutions

V/f pattern setting error.

Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.

HOA Keypad Display

Error Name

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred: C6-05 > 6 and C6-04 > C6-03

(carrier frequency lower limit is greater than the

upper limit).

If C6-05 ≤ 6, the drive operates at C6-03.

Correct the parameter settings.

The upper and lower limits between C6-02 and

C6-05 are contradictory.

oPE18

Online Tuning Parameter Setting Error
Parameters controlling online tuning are not set correctly.

HOA Keypad Display

Error Name

oPE28

Sequence Timer Error
One or more of the sequence timers is not set in the correct order.

Cause

Possible Solutions

5.4 Operator Programming Errors

276