P re-c ha rge, Figure 4.48 pre-charge inverse acting pid, Figure 4.49 pre-charge via low water di – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 232: P re-c ha rge & s lee p, Figure 4.50 pre-charge and sleep

Advertising
background image

R un

C omm an d

P re-C ha rge

C om plete via PID F eedba ck (R everse Acting PID )

“Pre-cha rge

Active”

M essage &

D igital Ou tpu t

(H 2-0x = A4)

Ou tpu t

F requen cy

P4-03

Pre-cha rge T im e

P4-02 – Pre-cha rge F requen cy

P4-01 – Pre-cha rge Le vel

b5-01 PID Se lect = 1 (Enab led) AND b5-09 Ou tpu t Le vel Se l = 1 (R ev C ha racter)

PID

F eedba ck

Figure 4.48 Pre-Charge Inverse Acting PID

R un

C omm an d

P re-C ha rge

C om plete via “Lo w W ater” digital inpu t (no rm ally ope n)

“Pre-cha rge

Active”

M essage &

D igital Ou tpu t

(H 2-0x = A4)

Ou tpu t

F requen cy

P4-03

Pre-cha rge T im e

P4-02 – Pre-cha rge F requen cy

P1-30 Lo w W ater D I Se l = 0 (N orm ally Ope n)

C losed

Ope n

Lo w W ater

D igital Inpu t

(N orm ally Ope n )

Figure 4.49 Pre-Charge via Low Water DI

P re-C ha rge & S lee p

W ake be low Pre-cha rge level then w ake abo ve Pr e-cha rge level

“Pre-cha rge

Active”

M essage &

D igital Ou tpu t

(H 2-0x = A4)

Ou tpu t

F requen cy

P4-03

Pre-cha rge T im e

P4-01 – Pre-cha rge Le vel

P1-04 – Start – D raw D n Le vel

P1-05

Start

D elay

P1-05

Start

D elay

Sleep ing

Sleep ing

PID

F eedba ck

b5-01 PID Se lect = 1 (Enab led ) AND b5-09 Ou tpu t Le vel Se l = 0 (N orm al C ha racter)
N OT E A: F eedba ck is be low the P4-01 level, a Pre-cha rge is pe rform ed.
N OT E B: F eedba ck is abo ve the P4-01 level, a Pre-cha rge is N OT pe rform ed.

NO

TE

B

NO

TE

A

P4-02

Figure 4.50 Pre-Charge and Sleep

4.6 Basic iQpump Setup and Application Preset Parameters

232

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising