A.3 drive watt loss data – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 316

Advertising
background image

Drive Model

Normal Duty

Rated Amps (A)

<1>

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

4A0414

414

3443

1295

4738

4A0515

515

4850

1668

6518

4A0675

675

4861

2037

6898

4A0930

930

8476

2952

11428

4A1200

1200

8572

3612

12184

<1> Value assumes the carrier frequency is 2 kHz (C6-02 = 1, 7, 8, 9, or A).

Table A.12 Watt Loss Three-Phase 600 V Class Three-Phase Models

Drive Model

Normal Duty

Rated Amps (A)

<1>

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

5A0003

2.7

21.5

23.3

44.8

5A0004

3.9

27.5

33.6

61.1

5A0006

6.1

28.1

43.7

71.8

5A0009

9.0

43.4

68.9

112.3

5A0011

11

56.1

88.0

144.0

5A0017

17

96.6

146.7

243.2

5A0022

22

99.4

178.3

277.7

5A0027

27

132.1

227.2

359.3

5A0032

32

141.6

279.9

421.5

5A0041

41

330.8

136.2

467.0

5A0052

52

427.8

166.2

594.0

5A0062

62

791.2

279.0

1070.2

5A0077

77

959.1

329.4

1288.6

5A0099

99

1253.2

411.7

1664.9

5A0125

125

1641

537

2178

5A0145

145

1860

603

2463

5A0192

192

2420

769

3189

5A0242

242

3100

1131

4231

<1> Value assumes the carrier frequency is 2 kHz (C6-02 = 1, 7, 8, 9, or A).

A.3 Drive Watt Loss Data

316

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising