H3: multi-function analog inputs – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 355

Advertising
background image

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

9D

High Suction

High Suction

Closed: The suction pressure has risen above the High Suction Pressure Detection

Level set in Q5-12 for longer than the High Suction Pressure Delay Time set in

Q5-13 or if there is a HISUC – High Suction Pressure Fault.

A2

Sleep Active

Sleep Active

Closed: The drive is not running due to the Sleep function (does not include Sleep

Boost).

A3

Start Delay

Start Delay

Closed: Feedback has risen above the start level (or fallen below for Inverse PID)

and the start timer is timing.

A4

Pre-Charge

Pre-Chg Active

Closed: Drive is in Pre-Charge mode.

A5

Anti-Jam Active

Anti-Jam Active

Closed: The anti-jam function is active (configured by P7-oo).

A9

Thrust Mode

Thrust Mode

Closed: The Thrust Bearing feature is active (output frequency is between 0 and

the value of P4-12).

AA

Utility Start Delay

Utility Delay

Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to

expire.

100 to

1AA

Function 0 to AA with

inverse output

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1oo to reverse the output signal of that specific function.

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H3-01

(0410)

Terminal A1 Signal

Level Selection

Term A1 Level

0: 0-10V,

(LowLim=0)

1: 0-10V, (BipolRef)

2: 4-20 mA

3: 0-20 mA

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A1 for a

current or voltage input signal.

Default: 0

Range: 0 to 3

219

H3-02

(0434)

Terminal A1 Function

Selection

Term A1 FuncSel

Sets the function of terminal A1.

Default: 0

Range: 0 to 32

219

H3-03

(0411)

Terminal A1 Gain

Setting

Terminal A1 Gain

Sets the level of the input value selected in H3-02 when 10 V is

input at terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

219

H3-04

(0412)

Terminal A1 Bias

Setting

Terminal A1 Bias

Sets the level of the input value selected in H3-02 when 0 V is

input at terminal A1.

Default: 0.0%

Min.: -999.9

Max.: 999.9

219

H3-05

(0413)

Terminal A3 Signal

Level Selection

Term A3 Level

0: 0-10V,

(LowLim=0)

1: 0-10V, (BipolRef)

2: 4-20 mA

3: 0-20 mA

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A3 for a

current or voltage input signal.

Default: 0

Range: 0 to 3

220

H3-06

(0414)

Terminal A3 Function

Selection

Term A3 FuncSel

Sets the function of terminal A3.

Default: 20

Range: 0 to 32

220

H3-07

(0415)

Terminal A3 Gain

Setting

Terminal A3 Gain

Sets the level of the input value selected in H3-06 when 10 V is

input at terminal A3.

Default: 100.0%

Min.: -999.9

Max.: 999.9

220

H3-08

(0416)

Terminal A3 Bias

Setting

Terminal A3 Bias

Sets the level of the input value selected in H3-06 when 0 V is

input at terminal A3.

Default: 0.0%

Min.: -999.9

Max.: 999.9

220

H3-09

(0417)

Terminal A2 Signal

Level Selection

Term A2 Level

0: 0-10V,

(LowLim=0)

1: 0-10V, (BipolRef)

2: 4-20 mA

3: 0-20 mA

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A2 for a

current or voltage input signal.

Default: 2

Range: 0 to 3

220

H3-10

(0418)

Terminal A2 Function

Selection

Term A2 FuncSel

Sets the function of terminal A2.

Default: B

Range: 0 to 32

221

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

355

B

Parameter List