When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.

2.0 V

10 V

-6.0 V

-10 V

E1-04

0

-100%

-150%

2.0 V

10 V

100 %

Frequency
reference

-25%

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

H3-01 = 1

100%

Analog Input

Voltage

Analog Input

Voltage

Figure 4.38 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-05: Terminal A3 Signal Level Selection

Determines the function assigned to analog input terminal A3.

No.

Name

Setting Range

Default

H3-05

Terminal A3 Signal Level Selection

0 to 3

0

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc. See the explanation provided for H3-01.

Refer to Setting 0: 0 to 10 Vdc on page 219

.

Setting 1: 0 to 10 Vdc Bipolar

The input level is -10 to 10 Vdc. See the explanation provided for H3-01.

Refer to Setting 1: 0 to 10 Vdc Bipolar on page

219

.

Setting 2: 4 to 20 mA
Setting 3: 0 to 20 mA

n

H3-06: Terminal A3 Function Selection

Determines the function assigned to analog input terminal A3.

No.

Name

Setting Range

Default

H3-06

Terminal A3 Function Selection

0 to 31

20

n

H3-07, H3-08: Terminal A3 Gain and Bias Setting

Parameter H3-07 sets the level of the selected input value that is equal to 10 Vdc input at terminal A3 (gain).
Parameter H3-08 sets the level of the selected input value that is equal to 0 V input at terminal A3 (bias).

No.

Name

Setting Range

Default

H3-07

Terminal A3 Gain Setting

-999.9 to 999.9%

100.0%

H3-08

Terminal A3 Bias Setting

-999.9 to 999.9%

0.0%

n

H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or

current input.

No.

Name

Setting Range

Default

H3-09

Terminal A2 Signal Level Selection

0 to 3

2

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc.

Refer to Setting 0: 0 to 10 Vdc on page 219

.

Setting 1: 0 to 10 Vdc Bipolar

The input level is -10 to 10 Vdc.

Refer to Setting 1: 0 to 10 Vdc Bipolar on page 219

.

Setting 2: 4 to 20 mA

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

4.6 Basic iQpump Setup and Application Preset Parameters

220