Related Parameters

No.

Parameter Name

Setting Values

A1-01

Access Level Selection

Default: 2

Range: 0 to 3

A1-03

Initialize Parameters

Default: 0

Range: 0 to 5550; 6008 to 6011; 7770

E2-01

Motor Rated Current

Default:

Min.: 10% of drive rated current

Max.: 200% of drive rated current

E2-04

Number of Motor Poles

Default: 2

Min.: 2

Max.: 48

P1-03

Feedback Device Scaling

Default: 145.0 PSI

Min.: 0.1

Max.: 6000.0

P1-11

High Feedback Level

Default: 0.0 PSI

Min.: 0.0

Max.: 6000.0

P1-06

Minimum Pump Speed

Default: 40.0 Hz

Min.: 0.0

Max.: [E1-04]

P1-04

Start / Draw Down Level

Default: 0.0

Min.: -999.9

Max.: 999.9

P2-02

Sleep Level

Default: 0.0 Hz

Min.: 0.0

Max.: 6000.0

P4-10

AUTO Mode Operator Run Power Down Storage

Default: 0

Range: 0, 1

P5-02

HAND Speed Reference 1

Default: 40.0 Hz

Min.: 0

Max.: [E1-04]

P5-04

HAND Key Function Selection

Default: 1

Range: 0, 1

Q1-01

PID Controller Setpoint 1

Default: 0.0

Min.: 0.0

Max.: 6000.0

U1-99

Anti-No-Flow Timer

No signal output available

4.5 iQpump Presets and Functions