B.11 P: Pump Parameters

u

P1: Pump Basic

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P1-01

(0C00) Pump Mode

Pump Mode

0: Drive Only

1: Contactor Lag

3: Memobus Network

0: Drive only

1: Contactor lag

3: MEMOBUS network

Default: 0

Range: 0, 1, 3

223

P1-02

(0C01) System Units

System Units

0: No Unit

1: PSI :lb/SqrInch

2: Pa:Pascals

3: Bar:Bar

4: "WC:InchOfWater

5: "Hg:Inch Mercury

6: ft: feet

7: m: meters

8: °F:DegFarenheit

9: °C:DegCelsius

10: %: Percent

25: Flow (use P6-04)

26:

Custom(P1-32~34)

0: No unit

1: PSI: Pounds per square inch

2: Pa: Pascals

3: Bar: Bar

4: ”WC: Inch of water

5: ”Hg: Inch of Mercury

6: ft: feet

7: m: meters

8: °F: Degrees Fahrenheit

9: °C: Degrees Celsius

10: Percent
25: Flow (Use P6-04)

<1>

26: Custom units

Default: 1

Range: 0 to 10;

25, 26

224

P1-03

(0C02)

Feedback Device

Scaling

FB Dev. Scaling

Sets the scaling of feedback device in user-set units.

Default: 145.0
PSI

<2>

Min.: 0.1

Max.: 6000.0

224

P1-04

(0C03) Start / Draw Down

Level

Start-DrawDn Lvl

The system starts when the feedback level drops below the start

level for the time set in P1-05. This level also specifies the wake-

up level when the drive is in Sleep Mode.

When this parameter is set to a negative value, the feedback level

must drop that amount below the setpoint.

Setting this parameter to 0.0 disables the function. When P1-01,

Pump Mode, is set to 3 (MEMOBUS network), this function is

active only on the first drive in the network.

Note:

When PID operates in reverse mode, the system

will start when the feedback has risen above the

start level for the time set to P1-05.

Default: 0.0 PSI

<2>

Min.: -999.9

Max.: 999.9

225

P1-05

(0C02) Start Level Delay Time S-Lev Delay Time

The system starts when the feedback level drops below the start

level for the time set in this parameter.

Default: 1 s

Min.: 0

Max.: 3600

225

P1-06

(0C05) Minimum Pump Speed Min. Pump Speed

Minimum frequency at which the drive will run. Applies to both

HAND and Automatic modes.

Note:

For minimum pump frequency, the drive will use

the highest setting from among P1-06, P4-12

(Thrust Bearing Frequency), or d2-02 (Reference

Lower Limit).

Default: 40.0 Hz

<3>

Min.: 0.0

Max.: [E1-04]

225

P1-07

(0C06)

<3>

Minimum Pump Speed

Units

MinPumpSpdUnits

0: Hz

1: RPM

Sets the units and decimal place for parameter P1-06.

0: Hz

1: RPM

Note:

Changing this parameter will reset the P1-06

default value.

Default: 0

Range: 0, 1

P1-08

(0C07) Low Feedback Level

Low FB Level

Sets the lower detection level for the PID feedback.

Default: 0.0 PSI

<2>

Min.: 0.0

Max.: 6000.0

225

P1-09

(0C08) Low Feedback Level

Fault Delay Time

Low Lvl FLT Time

Sets the amount of delay time from when the low feedback is

detected until the drive faults on an “LFB Low Feedback” fault.

Note:

1. This parameter is effective only when P1-10

is set to 0 (Fault).

2. When P1-01 is set to 3, parameter P9-18 uses

this value to calculate the quick de-stage

feedback level.

Default: 10 s

Min.: 0

Max.: 3600

225

B.11 P: Pump Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

373

B

Parameter List