P5: pump hand mode – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 381

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P4-24

(0D11) Low City Alarm Text

Low City Alarm Txt

0: Low Cty Pressure

1: Low Suction Pres

2: Low Watr in Tank

Selects the alarm message that will be displayed when a Low

City Pressure condition is detected.

0: Low city pressure

1: Low suction pressure

2: Low water in tank

Default: 0

Range: 0 to 2

P4-25

(0D12)

Remote Drive Disable

Selection

Rem Drv Dis Sel

0: Normally Open

1: Normally Closed

Selects the type of pressure switch connected to the “Remote

Drive Disable” digital input (H1-0o = 95).

0: Normally open (closed indicates the Remote Drive Disable

condition)

1: Normally closed (open indicates the Remote Drive Disable

condition)

Default: 1

Range: 0, 1

P4-26

(0D13) Remote Drive Disable

On-Delay

Drv Dis On-Delay

Sets the amount of time a Remote Drive Disable condition must

be present before the drive will stop.

Default: 0 s

Min.: 0

Max.: 1000

P4-27

(0D14) Remote Drive Disable

Off-Delay

Drv Dis OffDelay

Sets the amount of time a Remote Drive Disable condition must

be absent before the drive will run.

Default: 0 s

Min.: 0

Max.: 1000

P4-29

(0D16)

<3>

Lube Pump Message

Text

Lube Pump Text

0: Lube Pump

1: DigitalOut Delay

Selects which text is displayed when Lube Pump is active. Also

changes the text for the Lube Pump Digital Output selection

(H2-oo = 8B)

0: Lube Pump

1: Digital Out Delay

Default: 0

Range: 0, 1

P4-30

(0D17)

<3>

Lube Pump Active

During Run

Lube Pump DurRun

0: Disabled

1: Active DuringRun

When enabled, the Lube Pump digital output stays activated

after the timer expires and the drive starts to run normally. The

output is deactivated only when the drive stops, faults, or sleeps.

0: Disabled

1: Active During Run

Default: 0

Range: 0, 1

P4-31

(0D18) Lube Pump / Digital

Output Delay Timer

Lube Pump Time

Sets the amount of time to delay the drive output and to energize

the digital output (H2-oo = 8B) before the drive is allowed to

run.

Setting this parameter to 0.0 disables the function.

Default: 0.0 s

Min.: 0.0

Max.: 300.0

P4-32

(0D19)

<3>

Pre-charge Level 2

PreCharge Level2

For normal PI operation during Pre-charge 2, if the PI Feedback

signal rises above the P4-32 level, Pre-charge 2 is cancelled and

the drive resumes normal operation.

For inverse PI operation and during Pre-charge 2, if the PI

Feedback signal goes below the P4-32 level, Pre-charge 2 is

cancelled and the drive resumes normal operation.

When set to zero, Pre-charge 2 still runs when P4-07 is set, but

uses P4-01 to determine if normal operation should resume.

Default: 0.0 PSI

<1>

Min.: 0.0

Max.: 6000.0

<1> Unit is determined by P1-02, System Units, setting.
<2> Unit text is set by P1-18, Prime Loss Detection Method.
<3> Available in drive software versions PRG: 8551 and later.

u

P5: Pump HAND Mode

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P5-01

(0D2C) HAND Mode Ref

Source

Hand Mode Ref.

0: Analog Input

1: Hand Ref 1 (OPR)

Sets the HAND Mode reference.

0: Analog input

Note:

Analog input is defaulted to input A3 (0-10 V).

1: P5-02 (HAND reference)

Default: 1

Range: 0, 1

P5-02

(0D2D) HAND Reference 1

HAND Reference 1

Sets the frequency reference used when HAND Mode is active

and P5-01 is set to 1.

Default: 40.0 Hz

Min.: 0

Max.: [E1-04]

233

P5-03

(0D2E)

HAND/AUTO During

Run Selection

HAND/AUTO @ Run

0: Disabled

1: Enabled

Selects whether the drive will permit switching between HAND

and AUTO Modes while running.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

P5-04

(0D2F)

HAND Key Function

Selection

Oper HAND Key

0: Disabled

1: Enabled

Enables and disables the HAND key on the HOA keypad.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

234

B.11 P: Pump Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

381

B