Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 367

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-12

(04B8)

Ambient Temperature

Setting

Ambient Temp

Enter the ambient temperature. This value adjusts the oL2

detection level.

Default: 40 °C

Min.: -10

Max.: 50

L8-15

(04BB)

oL2 Characteristics

Selection at Low Speeds

OL2 Sel @ L-Spd

0: Disabled

1: Enabled

0: No oL2 level reduction below 6 Hz.

1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. Default: 1

Range: 0, 1

L8-18

(04BE)

Software Current Limit

Selection

Soft CLA Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

L8-19

(04BF)

Frequency Reduction

Rate during Overheat

Pre-Alarm

Fc Red dur OHAlm

Specifies the frequency reference reduction gain at overheat pre-

alarm when L8-03 = 4.

Default: 0.8

Min.: 0.1

Max.: 0.9

L8-32

(04E2)

Main Contactor and

Cooling Fan Power

Supply Failure

Selection

MC/FAN PS FltSel

0: Ramp to stop

1: Coast to stop

2: Fast-Stop

3: Alarm only

4: Run@L8-19 Rate

Determines drive response when a fault occurs with the internal

cooling fan.

0: Ramp to stop

1: Coast to stop

2: Fast stop (Decelerate to stop using the deceleration time set

to C1-09)

3: Alarm only (“FAn” will flash)

4: Continue operation at reduced speed as set to L8-19.

Default: 1

Range: 0 to 4

L8-35

(04EC)

Installation Method

Selection

Installation Sel

0: IP00/OpenChassis

1: Side-by-Side

2: IP20/Nema Type 1

3: ExternalHeatsink

0: IP00/Open-Chassis enclosure

1: Side-by-Side mounting

2: IP20/NEMA Type 1 enclosure

3: Finless model drive or external heatsink installation

Default:

<2> <3>

Range: 0 to 3

L8-38

(04EF)

Carrier Frequency

Reduction

Fc Reduct dur OL

0: Disabled

1: Active below 6Hz

2: Active @ any Spd

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default: 2

Range: 0 to 2

L8-40

(04F1)

Carrier Frequency

Reduction Off Delay

Time

Fc Reduct Time

Sets the time that the drive continues running with reduced

carrier frequency after the carrier reduction condition is gone.

Setting 0.00 s disables the carrier frequency reduction time.

Default: 0.5 s

Min.: 0.00

Max.: 2.00

L8-41

(04F2)

High Current Alarm

Selection

High Cur Alm Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled. An alarm is triggered at output currents above 150%

of drive rated current.

Default: 0

Range: 0, 1

L8-55

(045F)

Internal Braking

Transistor Protection

FC Sel dur OHAlm

0: Disabled

1: Enabled

0: Disabled. Disable when using a regen converter or optional

braking unit.

1: Protection enabled.

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 1

Range: 0, 1

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by the drive model:

Setting 2: Model code 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242
Setting 0: Model code 2A0250 to 2A0415 and 4A0208 to 4A1200.

B.8 L: Protection Function

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

367