4.6 Basic iQpump Setup and Application Preset Parameters

This section explains the basic settings required for initial drive operation. Checking these basic parameter settings will help

to ensure a successful drive start-up.

Refer to Parameter List on page 325

for a complete listing of drive parameters if more

information is required for parameters not listed in this section.

n

A1-01: Access Level Selection

Allows or restricts access to drive parameters.

No.

Parameter Name

Setting Range

Default

A1-01

Access Level Selection

0 to 3

2

Setting 0: Operation only

Access to only parameters A1-01, A1-04, and all U monitor parameters.

Setting 1: User Parameters

Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the

Setup Mode of the digital operator.

Setting 2: Advanced Access Level (A) and Setup Access Level (S)

All parameters can be viewed and edited.

Setting 3: Lock Parameters

Parameters that are normally visible in the advanced access level (A1-01 = 2) are still visible, but the only parameters that can

be changed are A1-01 and A1-04.
The Auto Tuning and Pump Quick Setup menus will not be displayed.

Figure 4.26 Help Message Example (Home Screen)

Notes on Parameter Access

• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2

parameters cannot be modified.

• If a digital input terminal programmed for “Program lockout” (H1-oo = 1B) is enabled, parameter values cannot be

modified, even if A1-01 is set to 1 or 2.

• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the

digital operator until an Enter command is issued to the drive from the serial communication.

n

A1-03: Initialize Parameters

Resets parameters to default values or performs an Application Preset for fan or pump applications. After initialization, the

setting for A1-03 automatically returns to 0.

No.

Parameter Name

Setting Range

Default

A1-03

Initialize Parameters

0, 1110, 2220, 3330, 5550,

6008, 6009, 6010, 6011,

7770, 7771

0

Setting 1110: User Initialize

Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to

“1: Set defaults”.

Note:

User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to

clear the user-defined default values.