No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Q2-09

(0E92)

Geothermal

Temperature Loss

Detection

Geotherm Loss Det

0: Disabled

1: Alarm Only

2: Fault

Selects the drive response when the signal from Terminal A2

falls below 3 mA or rises above 21 mA.

This parameter is only effective when H3-0o = 2 (4 to 20 mA)

and H3-0o = 21 (Geothermal Temperature).

0: Disabled

1: Alarm

2: Fault

Default: 1

Range: 0 to 2

Q2-10

(0E93) Geothermal Sleep Delay

Time

Geotherm Slp Dly

Set the length of time that the drive must be running at the speed

set in Q2-03, Minimum Geothermal Speed, before going to

sleep.

Default: 30 s

Min.: 0

Max.: 3600

Q2-11

(0E94)

Geothermal

Temperature Delta

Wake Level

Geotherm Wake Lvl

Sets the geothermal temperature that will wake up the drive.

The drive will wake up when one of the following conditions is

true:

Temperature > Q2-07 + Q2-11 OR

Temperature < Q2-06 - Q2-11

Setting this parameter to 0.0 will disable Geothermal Sleep

Mode.

Default: 0.0 °F

Min.: 0.0

Max.: 50.0

Q2-12

(0E95) Geothermal Sleep

Wake-Up Delay Time

Geotherm Wake Dly

Sets the length of time that the setting of Q2-11, Geothermal

Temperature Delta Wake Level, must be met to wake up the

drive.

Default: 5 s

Min.: 0

Max.: 3600

u

Q3: Output Current Limit

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Q3-01

(0EBC)

Output Current Limit

Select

Current Lim Sel

0: Disabled

1: Enabled

Enables and disables the output current regulator.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

Q3-02

(0EBD) Current Limit

Current Limit

Sets the current limit. Value is internally limited to 300% of the

drive rated current.

Default: 0.0 A

Min.: 0.0

Max.: 1000.0

Q3-10

(0EC5)

Ripple Regulator

Selection

Ripple Reg Sel

0: Disabled

1: Enabled

Enables and disables the single phase ripple regulator.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

Q3-11

(0EC6)

Ripple Regulator

Setpoint

Ripple Reg S.P.

Set as a percentage of the maximum amount of ripple allowed

before triggering an input phase loss fault.

Default: 95.0%

Min.: 0.0

Max.: 200.0

u

Q4: Water Level Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Q4-01

(0EEE) Water Level Selection

Water Level Sel

0: Disabled

1: Enabled

Enables and disables the water level control.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

Q4-02

(0EEF) Water Level Scaling

Water Lvl Scale

Sets the full scale (20 mA) output of the pressure transducer that

is connected to the analog input terminal programmed for

“WaterLvl/Suction” (H3-oo = 23).

Note:

1 PSI = 2.308 feet of water

Default: 100 PSI

Min.: 5

Max.: 500

Q4-03

(0EF0) Water Level Setpoint

Water Lvl Setpnt

Sets the amount of water above the sensor to which the drive

will attempt to regulate.

Default: 20.0 ft

Min.: 0.0

Max.: 1200.0

Q4-04

(0EF1) Minimum Water Level Min Water Level

Sets the level below which the amount of water must drop for

the time set in Q4-05 to put the drive to sleep.

Default: 10.0 ft

Min.: 0.0

Max.: 1200.0

Q4-05

(0EF2) Water Level Sleep

Delay Time

WL Sleep Dly Tm

Sets the length of time that the drive will delay after the water

level drops below the level set in Q4-04 before going to sleep.

Default: 5 s

Min.: 0

Max.: 3600

B.12 Q: PID Controller Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide