Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 383

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P6-05

(0D62) Flow Accumulation

Reset

Flow Accum Reset

Resets the accumulated flow and returns monitors U1-96 and

U1-97 to 0.

0: No reset

7770: Reset accumulation

8880: Set Accumulation (P6-31 to P6-34)

All other settings have no effect.

Note:

After this parameter is changed, the setting will

automatically return to “0”.

Default: 0

Min.: 0

Max.: 65535

P6-06

(0D63) Low Flow Level

Low Flow Level

Sets the level below which the flow must fall for longer than the

time set in P6-07 to trigger a Low Flow condition.

Setting this parameter to 0.0 will disable the function.

Default: 0.0
GPM

<1>

Min.: 0.0

Max.: 6000.0

P6-07

(0D64)

Low Flow Detection

Delay Time When

Already Running

Low Flow Tim Run

Sets the length of time that the flow rate must be below the level

set in P6-06 to detect a Low Flow condition.

Default: 10 s

Min.: 0

Max.: 6000

P6-08

(0D65) Low Flow Detection

Wait Time at Start

Low Flow Time St

Sets the length of time that the drive will wait after coming out

of a zero speed condition before activating Low Flow detection.

Default: 0.0 min

Min.: 0.0

Max.: 3600.0

P6-09

(0D66) Low Flow Select

Low Flow Sel

0: No Display

1: Alarm Only

2: Fault

3: Restart (P6-10)

Determines drive response when a Low Flow condition is

detected.

0: No display

1: Alarm only

2: Fault

3: Auto-restart (time set by P6-10)

Default: 1

Range: 0 to 3

P6-10

(0D67)

Low Flow Auto-Restart

Time

LowFlow Restart

Set the length of time that the drive will wait before attempting

an auto-restart of the Low Flow fault.

This parameter is effective only when P6-09 is set to 3.

Default: 3.0 min

Min.: 0.1

Max.: 6000.0

P6-11

(0D68) Accumulation Level -

Millions

AccumLvl*1000000

Sets the accumulated volume that will trigger the Accum Level

alarm, Accum Level fault, or the Accum Level digital output.

Accum Level is calculated using the following formula:

Level = (P6-11 * 1000000) + (P6-12 * 1000) + P6-13 + P6-14)

Default: 0 gal

<2>

Min.: 0

Max.: 65535

P6-12

(0D69) Accumulation Level -

Thousands

AccumLvl*1000

Default: 0 gal

<2>

Min.: 0

Max.: 999

P6-13

(0D6A) Accumulation Level -

Ones

AccumLvl*1

Default: 0 gal

<2>

Min.: 0

Max.: 999

P6-14

(0D6B) Accumulation Level -

Decimal

AccumLvl*0.0001

Default: 0.0000
gal

<2>

Min.: 0.0000

Max.: 0.9999

P6-15

(0D6C) Accumulation Behavior

Accum Behavior

0: No Display

1: Alarm Only

2: Fault

3: Fault-ResetAccum

4: Stop & Alarm

5: Stp/Alm/RstAccum

Determines drive response when the accumulated volume

reaches the P6-11 to P6-14 level.

0: No display

1: Alarm only

2: Fault

3: Fault - Auto flow accum reset

4: Stop and alarm

5: Stop, alarm, and reset flow accumulation

Default: 1

Range: 0 to 5

P6-16

(0D6D)

Flow Meter

Accumulator Units

Select

Accum Units

1: Gallons (gal)

2: Acre-Feet (A-F)

Selects whether the drive accumulates flow in gallons or acre-

feet.

1: Gallons (gal)

2: Acre-feet

Note:

Changing this parameter resets the accumulated

flow (U1-84 to U1-87) to zero.

Default: 1

Range: 1, 2

P6-17

(0D6E) High Flow Level

High Flow Level

Sets the level above which the flow must rise for the time set in

P6-18 to trigger a High Flow condition.

Default: 0.0
GPM

<1>

Min.: 0.0

Max.: 6000.0

B.11 P: Pump Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

383

B

Parameter List