H4: analog outputs – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 357

Advertising
background image

H3 Multi-Function Analog Input Settings

H3-oo

Setting

Function

LCD Display

Description

Page

F

Through mode

Not Used

Select this setting when using the terminal in a pass-through mode. The terminal

does not trigger a drive function but can be used as digital input for the controller

the drive is connected to.

10

Forward torque limit

Fwd Torque Limit

OLV

OLV

OLV

OLV

10 V = Motor rated torque

11

Reverse torque limit

Rev Torque Limit

OLV

OLV

OLV

OLV

10 V = Motor rated torque

12

Regenerative torque

limit

Regen Torq Limit

OLV

OLV

OLV

OLV

10 V = Motor rated torque

15

General torque limit

Torque Limit

OLV

OLV

OLV

OLV

10 V = Motor rated torque

16

Differential PID

feedback

PID Feedback 2

10 V = 100%

1F

Through mode

Not Used

Set this value when using the terminal in the pass-through mode.

20

HAND Frequency

Reference

Hand Freq. Ref.

Full scale: Max. frequency (E1-04)

21

Geothermal

Temperature

Geothermal Temp

Full scale: Q2-02 = 10 V (or 20 mA), Q2-01 = 0 V (or 4 mA)

This input is internally limited to -110.0 °F to +320.0 °F after gain and bias.

22

Flow Meter

Flow Meter

Full scale: P6-01

23

Water Level or Suction

Input

WaterLvl/Suction

When Water Level Control is enabled (Q4-01 = 1):

0 V or 4 mA = 0 (ft)

10 V or 20 mA = Q4-02 (PSI) * 2.308 ft/PSI OR
When Suction Pressure Control is enabled (Q5-01 = 1)

<2>

0 V or 4 mA = 9 (PSI)

10 V or 20 mA = Q5-02 (PSI) OR
When Vacuum Control is enabled (Q5-01 = 2)

<3>

0 V or 4 mA = 0 (”Hg)

10 V or 20 mA = Q5-02 (”Hg)

24

<1>

PI Feedback Backup

PI FdBack Backup

Full scale: FB Device Scaling (P1-03)

25

Secondary PI Setpoint

PI2 Setpoint

10 V = S3-02 (maximum output frequency)

26

Secondary PI Feedback PI2 Feedback

10 V = S3-02 (maximum output frequency)

<1> Available in drive software versions PRG: 8551 and later.
<2> When Pressure Control is enabled (Q5-01 = 1), the action of the analog input is normal. A higher voltage or current on the input causes a higher

pressure to be read in the drive.

<3> When Vacuum Control is enabled (Q5-01 = 2), the action of the analog input is reversed. A higher voltage or current on the input causes a lower

pressure (or higher level of vacuum) to be read in the drive.

u

H4: Analog Outputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H4-01

(041D)

Multi-Function Analog

Output Terminal FM

Monitor Selection

Term FM FuncSel

Selects the data to be output through multi-function analog

output terminal FM.

Set the desired monitor parameter to the digits available in

Uo-oo.

For example, enter “103” for U1-03.

Default: 102

Range: 000 to

999

221

H4-02

(041E)

Multi-Function Analog

Output Terminal FM

Gain

Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the

selected monitor value.

Default: 100.0%

Min.: -999.9

Max.: 999.9

221

H4-03

(041F)

Multi-Function Analog

Output Terminal FM

Bias

Terminal FM Bias

Sets the signal level at terminal FM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

221

B.7 H Parameters: Multi-Function Terminals

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

357