L2: momentary power loss ride-thru – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 361

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L1-19

(0444)

Operation at Thermistor

Disconnect (THo)

(NTC)

Tho Stop sel

Determines drive response when a thermistor disconnect fault

(THo) occurs.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time set

to C1-09)

3: Alarm only (“THo” will flash)

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 3

Range: 0 to 3

L1-20

(0445)

Operation at Motor

Overheat (oH5)

OH5 Stop sel

Determines drive response when a motor overheat fault (oH5)

occurs.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time set

to C1-09)

3: Alarm only (“oH5” will flash)

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 1

Range: 0 to 3

u

L2: Momentary Power Loss Ride-Thru

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L2-01

(0485)

Momentary Power Loss

Operation Selection

PwrL Selection

0: Disabled

1: Enbl with Timer

2: Enbl whl CPU act

3: KEB Mode

4: KEB Stop Mode

5: KEB Decel Stop

0: Disabled. Drive trips on Uv1 fault when power is lost.

1: Recover within the time set in L2-02. Uv1 will be detected if

power loss is longer than L2-02.

2: Recover as long as CPU has power. Uv1 is not detected.

3: KEB deceleration for the time set to L2-02.

4: KEB deceleration as long as CPU has power.

5: KEB deceleration to stop.

Default: 2

Range: 0 to 5

L2-02

(0486)

Momentary Power Loss

Ride-Thru Time

PwrL Ridethru t

Sets the Power Loss Ride-Thru time. Enabled only when

L2-01 = 1 or 3.

Default:

<1>

Min.: 0.0 s

Max.: 25.5 s

L2-03

(0487)

Momentary Power Loss

Minimum Baseblock

Time

PwrL Baseblock t

Sets the minimum wait time for residual motor voltage decay

before the drive output reenergizes after performing Power Loss

Ride-Thru.

Increasing the time set to L2-03 may help if overcurrent or

overvoltage occur during Speed Search or during DC Injection

Braking.

Default:

<1>

Min.: 0.1 s

Max.: 5.0 s

L2-04

(0488)

Momentary Power Loss

Voltage Recovery

Ramp Time

PwrL V/F Ramp t

Sets the time for the output voltage to return to the preset V/f

pattern during Speed Search.

Default:

<1>

Min.: 0.0 s

Max.: 5.0 s

L2-05

(0489)

Undervoltage Detection

Level (Uv1)

PUV Det Level

Sets the DC bus undervoltage trip level.

Default: 190
Vdc

<2> <3>

Min.: 150 Vdc
Max.: 210 Vdc

<3>

L2-06

(048A)

KEB Deceleration Time KEB Decel Time

Sets the time required to decelerate from the speed when KEB

was activated to zero speed.

Default: 0.00 s

Min.: 0.00
Max.: 6000.0

<4>

L2-07

(048B)

KEB Acceleration Time KEB Accel Time

Sets the time to accelerate to the frequency reference when

momentary power loss is over. If set to 0.0, the active

acceleration time is used.

Default: 0.00 s

Min.: 0.00
Max.: 6000.0

<4>

L2-08

(048C)

Frequency Gain at KEB

Start

KEB Freq Red

Sets the percentage of output frequency reduction at the

beginning of deceleration when the KEB Ride-Thru function is

started.

Reduction = (slip frequency before KEB) × L2-08 × 2

Default: 100%

Min.: 0

Max.: 300

B.8 L: Protection Function

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

361