L5: fault restart – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 364

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-05

(049D)

Frequency Reference

Loss Detection

Selection

Ref Loss Sel

0: Stop

1:

Run@L4-06PrevRef

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency

reference is lost.

Default: 0

Range: 0, 1

L4-06

(04C2)

Frequency Reference at

Reference Loss

Fref at Floss

Sets the percentage of the frequency reference that the drive

should run with when the frequency reference is lost.

Default: 80.0%

Min.: 0.0

Max.: 100.0

L4-07

(0470)

Speed Agreement

Detection Selection

Freq Detect Sel

0: No Detection @BB

1: Always Detected

0: No detection during baseblock.

1: Detection always enabled.

Default: 0

Range: 0, 1

u

L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(049E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after

the following faults occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2,

oL3, oL4, STo, Uv1.

Default: 5

Min.: 0

Max.: 10

L5-02

(049F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

L5-04

(046C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault

restarts.

Default: 20.0 s

Min.: 10.0

Max.: 3600.0

L5-40

(0670)

Low Feedback Fault

Retry Selection

Low Feedback

0: No retry

1: Retry

Determines whether the LFB-Low Feedback fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-41

(0671)

High Feedback Fault

Retry Selection

High Feedback

0: No retry

1: Retry

Determines whether the HFB-High Feedback fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-42

(0672)

Feedback Loss Fault

Retry Selection

Feedback Loss

0: No retry

1: Retry

Determines whether the FBL-Feedback Loss fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-50

(067A)

Setpoint Not Met Retry

Selection

SetPoint Not Met

0: No retry

1: Retry

Determines whether the NMS-Setpoint not Met fault can be

auto-restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-51

(067B)

Loss of Prime Fault

Retry Selection

High Feedback

0: No retry

1: Retry

Determines whether the LOP-Loss of Prime fault can be auto-

restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-52

(067C)

Pump Over Cycle Fault

Retry Selection

Pump Over Cycle

0: No retry

1: Retry

Determines whether the POC-Pump Over Cycle fault can be

auto-restarted.

0: No retry

1: Retry

Default: 0

Range: 0, 1

L5-53

(067D)

Volute-TStat Retry

Selection

Volute-TStat Flt

0: No retry

1: Retry

Determines whether the Volute T-Stat fault can be auto-

restarted.

0: No retry

1: Retry

Note:

The drive will restart only after the Volute-Tstat

digital input deactivates and the L5-04 timer

expires.

Default: 0

Range: 0, 1