C3: Slip Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C3-01

(020F) Slip Compensation Gain Slip Comp

Sets the gain for the motor slip compensation function used for

motor 1.

Default: 0.0 (V/

f)

1.0 (OLV)

Min.: 0.0

Max.: 2.5

C3-02

(0210)

Slip Compensation

Primary Delay Time

Slip Comp Time

Adjusts the slip compensation function delay time used for

motor 1.

Default: 2000 ms

(V/f)

200 ms (OLV)

Min.: 0

Max.: 10000

C3-03

(0211)

Slip Compensation

Limit

Slip Comp Limit

Sets an upper limit for the slip compensation function as a

percentage of motor rated slip for motor 1 (E2-02).

Default: 200%

Min.: 0

Max.: 250

C3-04

(0212)

Slip Compensation

Selection during

Regeneration

Slip Comp Regen

0: Disabled

1: Above 6 Hz

2: Lowst possbl spd

0: Disabled.

1: Enabled above 6 Hz

2: Enabled whenever slip compensation is possible.

Default: 0

Range: 0 to 2

C3-05

(0213)

Output Voltage Limit

Operation Selection

Output V Lim Sel

0: Disabled

1. Enabled

OLV

OLV

OLV

OLV

0: Disabled.

1: Enabled. Automatically decreases motor flux when output

voltage saturation is reached.

Default: 0

Range: 0, 1

C3-16

(0261)

Output Voltage Limit

Operation Start Level

(Percentage

Modulation)

Output V Lim Sta

Sets the output voltage limit operation start level (percentage

modulation) when C3-05 is enabled.

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 85.0%

Min.: 70.0

Max.: 90.0

C3-17

(0262)

Maximum Output

Voltage Limit Level

(Percentage

Modulation)

Output V Lim Max

Sets the output voltage limit operation determined by C3-18

(percentage modulation) when C3-05 is enabled.

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 90.0%

Min.: 85.0

Max.: 100.0

C3-18

(0263)

Output Voltage Limit

Level

Output V Lim lev

Sets the maximum percentage of output voltage reduction when

C3-05 is enabled.

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default: 90.0%

Min.: 30.0

Max.: 100.0

u

C4: Torque Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C4-01

(0215)

Torque Compensation

Gain

Torq Comp Gain

Sets the gain for the automatic torque (voltage) boost function

and helps to produce better starting torque. Used for motor 1.

Default: 1.00

Min.: 0.00

Max.: 2.50

C4-02

(0216)

Torque Compensation

Primary Delay Time 1

Torq Comp Time

Sets the torque compensation filter time.

Default: 200 ms

(V/f)

20 ms (OLV)

Min.: 0

Max.: 60000

C4-03

(0217)

Torque Compensation

at Forward Start

F TorqCmp@start

OLV

OLV

OLV

OLV

Sets torque compensation at forward start as a percentage of

motor torque.

Default: 0.0%

Min.: 0.0

Max.: 200.0

C4-04

(0218)

Torque Compensation

at Reverse Start

R TorqCmp@start

OLV

OLV

OLV

OLV

Sets torque compensation at reverse start as a percentage of

motor torque.

Default: 0.0%

Min.: -200.0

Max.: 0.0

C4-05

(0219)

Torque Compensation

Time Constant

TorqCmp Delay T

OLV

OLV

OLV

OLV

Sets the time constant for torque compensation at forward start

and reverse start (C4-03 and C4-04).

Default: 10 ms

Min.: 0

Max.: 200