C.5 Drive Operations by MEMOBUS/Modbus

The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings. This

section explains the functions that can be used and related parameter settings.

u

Observing the Drive Operation

A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter

settings (except for H5-ooparameters):
• observe drive status and drive control terminal status from a PLC.
• read and write parameters.
• set and reset faults.
• set multi-function inputs.

Note:

Input settings from the input terminals (S1 to S8) and from MEMOBUS/Modbus communications are both linked by a logical OR operation.

u

Controlling the Drive

Select an external reference and adjust the parameters in

Table C.2

accordingly to start and stop the drive or set the frequency

reference using MEMOBUS/Modbus communications.

Table C.2 Setting Parameters for Drive Control from MEMOBUS/Modbus

Reference Source

Parameter

Name

Required Setting

External Reference 1

b1-01

Frequency Reference Selection 1

2

b1-02

Run Command Selection 1

2

External Reference 2

b1-15

Frequency Reference Selection 2

2

b1-16

Run Command Selection 2

2

Refer to b1-01: Frequency Reference Selection 1 on page 209

and

Refer to b1-02: Run Command Selection 1 on page

211

for details on external reference parameter selections.

C.5 Drive Operations by MEMOBUS/Modbus

420

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide