Contents

00C7H

Fault Contents 10
bit 0

High Water Level (HWL)

bit 1

High Suction (HISUC)

bit 2

Water Level Loss (WLL)

bit 3

SuctionPres Loss (SPL)

bit 4

Volute-TStat Flt (VLTS)

bit 5 to F

Reserved

00C8H

Alarm Contents 2
bit 0

Undervoltage (Uv)

bit 1

Overvoltage (ov)

bit 2

Heatsink Overheat (oH)

bit 3

Drive Overheat (oH2)

bit 4

Overtorque 1 (oL3)

bit 5

Overtorque 2 (oL4)

bit 6

Run Commands Input Error (EF)

bit 7

Drive Baseblock (bb)

bit 8

External Fault 3, input terminal S3 (EF3)

bit 9

External Fault 4, input terminal S4 (EF4)

bit A

External Fault 5, input terminal S5 (EF5)

bit B

External Fault 6, input terminal S6 (EF6)

bit C

External Fault 7, input terminal S7 (EF7)

bit D

External Fault 8, input terminal S8 (EF8)

bit E

Cooling Fan Error (FAn)

bit F

Reserved

00C9H

Alarm Contents 3
bit 0, 1

Reserved

bit 2

Digital Operator Connection Fault (oPr)

bit 3

MEMOBUS/Modbus Communication Error (CE)

bit 4

Option Communication Error (bUS)

bit 5

Serial Communication Transmission Error (CALL)

bit 6

Motor Overload (oL1)

bit 7

Drive Overload (oL2)

bit 8

Reserved

bit 9

Option Card External fault (EF0)

bit A, B

Reserved

bit C

Serial Communication Transmission Error (CALL)

bit D

Undertorque Detection 1 (UL3)

bit E

Undertorque Detection 2 (UL4)

bit F

MEMOBUS/Modbus Test Mode Fault (SE)

00CAH

Alarm Contents 4
bit 0

Reserved

bit 1

Motor Overheat 1 (PTC Input) (oH3)

bit 2 to 5

Reserved

bit 6

PID Feedback Loss (FbL)

bit 7

PID Feedback Loss (FbH)

bit 9

Drive Disabled (dnE)

bit A to F

Reserved

C.9 MEMOBUS/Modbus Data Table