Name

LCD Display

Description

Values

Page

P9-27

(0E0E) Network Recovery

Network Recovery

0: Automatic

1: Slave/Resume

2: Slave/Stop

3: Fault MSL

Determines the drive response when no messages are received

from the master for the time set in P9-26.

0: Automatic. The drive will attempt to assume master

functionality.

1: Slave/Resume. The drive will continue running when the

master is lost and will wait for a master to come online.

2: Slave/Stop. The drive will stop running when the master is

lost and will wait for a master to come online.

3: Fault MSL. Fault the drive with an MSL (Master Lost).

Default: 0

Range: 0 to 3

P9-28

(0E0F) NETSCAN Alarm Time NETSCAN AlrmTime

Sets the amount of time that the slave drives will wait for a

message from the master before displaying a NETSCAN alarm.

Default: 2.0 s

Min.: 1.0

Max.: 10.0

P9-29

(0E10) Net Start Delay

Net Start Delay

Sets the amount of time that the network will wait before

selecting and starting the lead drive after the first drive on the

network has been put on AUTO Mode.

Default: 2.0 s

Min.: 0.0

Max.: 60.0

P9-30

(0E11) Lag Drive Speed

Follower Gain

Lag Followr Gain

Sets the gain to be applied to the speed of the current lead drive

when P9-05 is set to 3. The bias to be applied is set in P9-31.

Default: 100.0%

Min.: 0.0

Max.: 300.0

P9-31

(0E12) Lag Drive Speed

Follower Bias

Lag Followr Bias

Sets the bias to be applied to the speed of the current lead drive

when P9-05 is set to 3. The gain to be applied is set in P9-30.

Default: 0.00 Hz

Min.: -60.0

Max.: 60.0

P9-32

(0E13) Lag Follower

Deceleration Time

Lag Followr Dcel

Sets the deceleration time when the P9-33 timer is running and

the drive is running as Lag Drive Speed Follower (P9-05 is set

to 3).

Default: 60.0 s

Min.: 0.0

Max.: 1000.0

P9-33

(0E14)

Lag Follower

Deceleration Time

Active Time

Lag Followr Dtim

Sets the time during which the deceleration time set in P9-32 is

effective. The drive will use the standard deceleration rate when

it expires.

Setting this parameter to 0.0 disables the function.

Default: 0.0 s

Min.: 0.0

Max.: 360.0

P9-34

(0E15) Low Feedback Quick

De-Stage

Low FB De-stage

Sets the low feedback level that will trigger a quick de-stage.

The quick de-stage ignores parameters P9-12 and P9-15 and

only uses an internal 2 second delay.

Setting this parameter to 0.0 disables the function.

Default: 0.0 PSI

<1>

Min.: 0.0

Max.: 6000.0

P9-35

(0E16)

<2>

Alternation

Stabilization Time

AltStabilizeTime

Sets the maximum amount of time the drive will stay running

when it was called to alternate-out. The drive is put into the

Alternation Stabilization Mode during this period.

Setting this parameter to 0 disables the function.

Default: 0 s

Min.: 0

Max.: 1000

P9-36

(0E17)

<2>

Alternation

Stabilization Bias

AltStabilizeBias

Sets the minimum amount of PID error applied to the drive

during Alternation Stabilization Mode. A lower value can cause

it to remain running longer, while a higher value will make the

transition faster at the cost of a more significant pressure change.

Set as a percentage of P1-03, System Unit Scaling.

Default: 0.50%

Min.: 0.00

Max.: 10.00

P9-40

(0E1B) Flow Rate Source

Flow Rate Source

0: Analog Only

3: Network Only

Defines the flow meter input source when P1-01, Pump Mode,

is set to 3 (MEMOBUS network).

0: Analog

3: Network

Default: 0

Range: 0, 3

P9-41

(0E1C) Add Flow Level

Add Flow Lvl

When P9-08 is set to 3 and the flow rate rises above this level

multiplied by the number of pumps running for the time set in

P9-11, the lead drive will request for a new lead drive through

the iQpump MEMOBUS network.

Default: 0.0

GPM

Min.: 0.0

Max.: 6000.0

P9-42

(0E1D) Remove Flow Level

Remove Flow Lvl

When P9-12 is set to 3 and the flow rate falls below this level

multiplied by the number of pumps running - 1 for the time set

in P9-15, the lead drive will request to be removed from the

system through the iQpump MEMOBUS network.

Default: 0.0

GPM

Min.: 0.0

Max.: 6000.0

P9-50

(0E25)

Water Level/Suction

Pressure Source

WL/SP Source

0: Analog only

1: Ana->Net, No Alrm

2: Ana->Net, Alarm

3: Network only

Sets the signal to use for Water Level Control (Q4-oo) or

Suction Pressure Control (Q5-oo) when P1-01, Pump Mode,

is set to 3 (MEMOBUS network).

0: Analog only

1: Ana->Net, No Alrm

2: Ana->Net, Alarm

3: Network only

Default: 0

Range: 0 to 3

B.11 P: Pump Parameters