Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 221

Advertising
background image

Setting 3: 0 to 20 mA

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 32

B

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection

Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM.

Refer to U1:

Operation Status Monitors on page 401

for a list of all monitors. The “Analog Output Level” column indicates whether a

monitor can be used for analog output.
Example: Enter “103” for U1-03.

No.

Name

Setting Range

Default

H4-01

Multi-Function Analog Output Terminal FM Monitor Selection

000 to 999

102

H4-04

Multi-Function Analog Output Terminal AM Monitor Selection

000 to 999

103

A setting of 031 or 000 applies no drive monitor to the analog output. With either of these settings, the output level of the

terminals FM and AM can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).

n

H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias

H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias

Parameters H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at

100%. Parameters H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected monitor

is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or 4 mA. The

output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and

H4-08.

Figure 4.39

illustrates how gain and bias settings work.

No.

Name

Setting Range

Default

H4-02

Multi-Function Analog Output Terminal FM Gain

-999.9 to 999.9%

100.0%

H4-03

Multi-Function Analog Output Terminal FM Bias

-999.9 to 999.9%

0.0%

H4-05

Multi-Function Analog Output Terminal AM Gain

-999.9 to 999.9%

50.0%

H4-06

Multi-Function Analog Output Terminal AM Bias

-999.9 to 999.9%

0.0%

Using Gain and Bias to Adjust Output Signal Level

The output signal is adjustable while the drive is stopped.

Terminal FM

1.

View the value set to H4-02 (Terminal FM Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in H4-01 will be output from terminal FM.

2.

Adjust H4-02 viewing the monitor connected to the terminal FM.

3.

View the value set to H4-03 on the digital operator; terminal FM will output a voltage equal to 0% of the parameter

being set in H4-01.

4.

Adjust H4-03 viewing the output signal on the terminal FM.

4.6 Basic iQpump Setup and Application Preset Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

221

4

Start-Up Programming & Operation

Advertising