P9-51

(0E26)

Low Water Level/

Suction Pressure Turn-

Off Method

Low WL Turn-Off

0: Disabled

1: Enabled

Determines the MEMOBUS multiplex response to Water Level

or Suction Pressure.

0: Disabled
• Water level does not have an effect on Idle or Lag drives
• Water level will not cause alternation
1: Enabled
• A drive is considered offline when the Water Level/Suction

Pressure is below the wake-up level set in Q4-06/Q5-06.

• A Lag drive is removed when the Water Level/Suction

Pressure is below the wake-up level set in Q4-06/Q5-06.

• A Lead drive is alternated if in Level Control/Suction

Pressure while the Water Level is below the septoint set in

Q4-03/Q5-03.

Default: 0

Range: 0, 1

P9-60

(0E2F)

Geothermal

Temperature Source

Geo Temp Source

0: Analog only

1: Ana->Net, No Alrm

2: Ana->Net, Alarm

3: Network only

0: Analog only

1: Ana->Net, No Alrm

2: Ana->Net, Alarm

3: Network only

Default: 0

Range: 0 to 3

P9-99

(0E56)

Network Compatibility

Selection

Network Comp Sel

0: A-Ver: 30034

1: B-Ver: 30035/36

2: iQ SmartNetwork

Determines the communication compatibility for the iQPump

MEMOBUS network.

0: A-Ver: 30034

1: B-Ver: 30035/36

2: iQ SmartNetwork

Default: 2

Range: 0 to 2

<1> Unit is determined by P1-02, System Units, setting.
<2> Available in drive software versions PRG: 8551 and later.

B.11 P: Pump Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

389

B

Parameter List