Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 429
Register No.
Contents
0029H
Fault Contents 2
bit 0
IGBT Short Circuit (SC)
bit 1
Ground Fault (GF)
bit 2
Input Phase Loss (PF)
bit 3
Output Phase Loss (LF)
bit 4
Braking Resistor Overheat (rH)
bit 5
Reserved
bit 6
Motor Overheat 2 (PTC input) (oH4)
bit 7 to bit F
Reserved
002AH
Alarm Contents 1
bit 0, 1
Reserved
bit 2
Run Command Input Error (EF)
bit 3
Drive Baseblock (bb)
bit 4
Overtorque Detection 1 (oL3)
bit 5
Heatsink Overheat (oH)
bit 6
Overvoltage (ov)
bit 7
Undervoltage (Uv)
bit 8
Cooling Fan Error (FAn)
bit 9
MEMOBUS/Modbus Communication Error (CE)
bit A
Option Communication Error (bUS)
bit B
Undertorque Detection 1/2 (UL3/UL4)
bit C
Motor Overheat (oH3)
bit D
PID Feedback Loss (FbL, FbH)
bit E
Reserved
bit F
Serial Communication Transmission Error (CALL)
002BH
Input Terminal Status
bit 0
Terminal S1 Closed
bit 1
Terminal S2 Closed
bit 2
Terminal S3 Closed
bit 3
Terminal S4 Closed
bit 4
Terminal S5 Closed
bit 5
Terminal S6 Closed
bit 6
Terminal S7 Closed
bit 7
Terminal S8 Closed
bit 8 to bit F
Reserved
C.9 MEMOBUS/Modbus Data Table
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
429
C
MEMOBUS/Modbus Communications