Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 311

Advertising
background image

u

Three-Phase 600 V Class Drive Models 5A0041 to 5A0099

Table A.8 Power Ratings Continued (Three-Phase 600 V Class)

Item

Specification

Drive Models

5A0041

5A0052

5A0062

5A0077

5A0099

Maximum Applicable Motor Capacity (HP)

<1>

ND Rating

40

50

60

75

100

Input

Input Current (A)

<2>

ND Rating

44

54

66

80

108

Rated Voltage

Rated Frequency

Three-phase 500 to 600 Vac 50/60 Hz

Allowable Voltage Fluctuation

-10 (-15) to +10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

ND Rating

50

62

75

91

123

Output

Rated Output Capacity (kVA)

<3>

ND Rating

<4>

41

52

62

77

99

Rated Output Current (A)

ND Rating

<4>

41

52

62

77

99

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

User-adjustable between 1 and 10 kHz

<4>

User-

adjustable

between 1 and

8 kHz

<4>

Maximum Output Voltage (V)

Three-phase 500 to 600 V (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings

raise the carrier frequency and require current derating.

A.1 Power Ratings

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

311

A

Specifications