Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 356

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H3-11

(0419)

Terminal A2 Gain

Setting

Terminal A2 Gain

Sets the level of the input value selected in H3-10 when 10 V

(20 mA) is input at terminal A2.

Default: 100.0%

Min.: -999.9

Max.: 999.9

221

H3-12

(041A) Terminal A2 Bias

Setting

Terminal A2 Bias

Sets the level of the input value selected in H3-10 when 0 V (0

or 4 mA) is input at terminal A2.

Default: 0.0%

Min.: -999.9

Max.: 999.9

221

H3-13

(041B)

Analog Input Filter

Time Constant

A1/A2 Filter T

Sets a primary delay filter time constant for terminals A1, A2,

and A3. Used for noise filtering.

Default: 0.03 s

Min.: 0.00

Max.: 2.00

H3-14

(041C)

Analog Input Terminal

Enable Selection

A1/A2 Sel

1: A1 Available

2: A2 Available

3: A1/A2 Available

4: A3 Available

5: A1/A3 Available

6: A2/A3 Available

7: All Available

Determines which analog input terminals will be enabled when

a digital input programmed for “Analog input enable”

(H1-oo = C) is activated.

1: Terminal A1 only

2: Terminal A2 only

3: Terminals A1 and A2 only

4: Terminal A3 only

5: Terminals A1 and A3

6: Terminals A2 and A3

7: All terminals enabled

Default: 7

Range: 1 to 7

H3-16

(02F0) Terminal A1 Offset

Term A1 Offset

Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0

Min.: -500

Max.: 500

H3-17

(02F1) Terminal A2 Offset

Term A2 Offset

Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0

Min.: -500

Max.: 500

H3-18

(02F2) Terminal A3 Offset

Term A3 Offset

Adds an offset when the analog signal to terminal A3 is at 0 V. Default: 0

Min.: -500

Max.: 500

H3 Multi-Function Analog Input Settings

H3-oo

Setting

Function

LCD Display

Description

Page

0

Frequency bias

Freq Ref Bias

10 V = E1-04 (maximum output frequency)

1

Frequency gain

Freq Ref Gain

0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting

of -100 to 0%.

2

Auxiliary frequency

reference 1

Aux Reference1

10 V = E1-04 (maximum output frequency)

3

Auxiliary frequency

reference 2

Aux Reference2

10 V = E1-04 (maximum output frequency)

4

Output voltage bias

Voltage Bias

V/f

V/f

10 V = E1-05 (motor rated voltage)

5

Accel/decel time gain

Acc/Dec Change

10 V = 100%

6

DC Injection Braking

current

DC Brake Current

10 V = Drive rated current

7

Overtorque/

undertorque

detection level

Torque Det Level

10 V = Drive rated current (V/f)

8

Stall Prevention level

during run

Stall Prev Level

V/f

V/f

10 V = Drive rated current

9

Output frequency lower

limit level

Ref Lower Limit

10 V = E1-04 (maximum output frequency)

B

PID feedback

PID Feedback1

10 V = 100%

C

PID setpoint

PID Set Point

10 V = 100%

D

Frequency bias

Freq Ref Bias 2

10 V = E1-04 (maximum output frequency)

E

Motor Temperature

(PTC Input)

E Motor PTC

10 V = 100%

Note:

A 12 kΩ resistor must be connected between terminals A1, A2, or

A3 and V+ for PTC functionality.