Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 419

Advertising
background image

n

H5-11: Communications Enter Function Selection

Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.

Refer

to Enter Command on page 444

.

No.

Name

Setting Range

Default

H5-11

Communications Enter Function Selection

0 or 1

0

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter

change, not for each single parameter.

Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

n

H5-12: Run Command Method Selection

Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications

(b1-02, b1-16 = 2).

No.

Name

Setting Range

Default

H5-12

Run Command Method Selection

0 or 1

0

Setting 0: FWD/Stop, REV/Stop

Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will

start and stop the drive in reverse.

Setting 1: Run/Stop, FWD/REV

Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.

C.4 MEMOBUS/Modbus Setup Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

419

C

MEMOBUS/Modbus Communications

Advertising