Starting Auto-Tuning

WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or

serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.

WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the

motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.

NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in improper

operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.

Enter the required information from the motor nameplate. Press

to proceed to the Auto-Tuning start display.

Note:

These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.

Step

Display/Result

1. After entering the data listed on the motor nameplate, press

to confirm.

- A.TUNE -

0.00 Hz/ 0.00A

Tuning Ready ?

DRV

Auto-Tuning

Rdy

ESC

FWD

Press RUN key

2.

Press

to activate Auto-Tuning.

flashes. The drive begins by injecting current

into the motor for about 1 min, and then starts to rotate the motor.

Note:

The first digit on the display indicates which motor is undergoing

Auto-Tuning. The second digit indicates the type of Auto-Tuning being

performed.

- A.TUNE -

X.XX Hz/ X.XXA

DRV

Tune Proceeding

Rdy

FWD

<

<<

<<< >>>

>>

>

3. Auto-Tuning finishes in approximately one to two minutes.

- MODE -

End

Tune Successful

DRV

FWD

RESET

5.8 Auto-Tuning

288

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide