Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 275

Advertising
background image

Settings for N.C. and N.O. input for the following

functions were selected simultaneously:
• External Search Command 1 and External

Search Command 2 (61 vs. 62)

• Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
• KEB for Momentary Power Loss and High Slip

Braking

(65, 66, 7A, 7B vs. 68)

• Motor Switch Command and Accel/Decel Time

2 (16 vs. 1A)

• KEB Command 1 and KEB Command 2 (65, 66

vs. 7A, 7B)

• FWD Run Command (or REV) and FWD/REV

Run Command (2-wire) (40, 41 vs. 42, 43)

• External DB Command and Drive Enable (60

vs. 6A)

• Motor Switch Command and Up 2/Down 2

Command (16 vs. 75, 76)

• Check if contradictory settings have simultaneously been assigned to the multi-function input

terminals.

• Correct setting errors.

One of the following settings was entered while

H1-oo = 2 (External Reference 1/2):
• b1-15 = 4 (Pulse Train Input) but the pulse train

input selection is not set for the frequency

reference (H6-01 > 0)

• b1-15 or b1-16 set to 3 but no option card is

connected

• Although b1-15 = 1 (Analog Input) and H3-02

or H3-10 are set to 0 (Frequency Bias)

Correct the settings for the multi-function input terminal parameters.

H2-oo is set to 38 (Drive Enabled) and H1-oo

is not set to 6A (Drive Enable).

HOA Keypad Display

Error Name

oPE04

Initialization Required, Term <–> Ctrl Chg

Cause

Possible Solutions

The drive, control board, or terminal board have

been replaced and the parameter settings between

the control board and the terminal board no longer

match.

Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the drive. Initialize

parameters after drive replacement by setting A1-03 to 1110 or 2220.

HOA Keypad Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card

(b1-01 = 3) and an input option card is not

connected to the drive.

Reconnect the input option card to the drive.

The Run command is assigned to an option card

(b1-02 = 3) and an input option card is not

connected to the drive.
Frequency reference is assigned to the pulse train

input (b1-01 = 4) and terminal RP is not set for

frequency reference input (H6-01 > 0)

Set H6-01 to 0.

HOA Keypad Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06 and PID

functions conflict.

Cause

Possible Solutions

At least two analog input terminals are set to the

same function (i.e., at least two of these parameters

have the same setting: H3-02, H3-10, or H3-06).

Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02, H3-10, or

H3-06 simultaneously.

5.4 Operator Programming Errors

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

275

5

Troubleshooting