Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 272

Advertising
background image

HOA Keypad Display

Minor Fault Name

UL3

Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable

time (L6-03).

Cause

Possible Solution

Parameter settings are not appropriate for

the load

Check the settings of parameters L6-02 and L6-03.

There is a fault on the machine side

Check the load for any problems.

HOA Keypad Display

Minor Fault Name

UL4

Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable

time (L6-06).

Cause

Possible Solution

Parameter settings are not appropriate for

the load

Check L6-05 and L6-06 settings

There is a fault on the machine side

Check the load for any problems.

HOA Keypad Display

Minor Fault Name

UL6

Motor Underload
The load has fallen below the underload curve defined in L6-14.

Cause

Possible Solution

The output current has fallen below the

motor underload curve defined in L6-14 for

longer than the time set to L6-03

Adjust the value set to L6-14 so that output current remains above the motor underload curve during normal

operation.

HOA Keypad Display

Minor Fault Name

Uv

Undervoltage
One of the following conditions was true when the drive was stopped and a Run command was entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage

is under L2-05.

Cause

Possible Solution

Phase loss in the drive input power.

Check for wiring errors in the main circuit drive input power. Correct the wiring.

Loose wiring in the drive input power

terminals.

• Ensure the terminals have been properly tightened.
Apply the tightening torque to the terminals as specified.

Refer to Main Circuit Wire Gauges and

Tightening Torque on page 134

.

There is a problem with the drive input

power voltage.

• Check the voltage.
• Lower the voltage of the drive input power so that it is within the limits listed in the specifications.

Drive internal circuitry is worn.

• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing

the control board, contact Yaskawa or your nearest sales representative.

The drive input power transformer is too

small and voltage drops when the power is

switched on.

• Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
• Check the capacity of the drive input power transformer.

Air inside the drive is too hot.

Check the temperature inside the drive.

The CHARGE light is broken or

disconnected.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

voF

Output Voltage Detection Error
Problem detected with the voltage on the output side of the drive.

Cause

Possible Solution

Hardware is damaged. Internal drive

module MC / FAN overheat protection

circuit board is due to abnormal ambient

operating power.

• Lower ambient temperature.
• Replace the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or a Yaskawa representative.

5.3 Alarm Detection

272

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising